Kabeltværsnit for 600 Ampere ved 90 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 600 A over 90 m ved 400V.
Copper Cable (≤3% Drop)2× 400 mm²Drop: 2.5V (0.62%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 8.25V (2.06%)
Voltage at Load397.5 VLine Loss: 2600.1 W
Max Power & Breaker415.69 kW600A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 90m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1334.37 V (333.59%) | 0.0 V | 2201.09 V (550.27%) | 1386720.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 800.62 V (200.16%) | 0.0 V | 1320.65 V (330.16%) | 832032.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 500.39 V (125.1%) | 0.0 V | 825.41 V (206.35%) | 520020.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 333.59 V (83.4%) | 66.4 V | 550.27 V (137.57%) | 346680.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 200.16 V (50.04%) | 199.8 V | 330.16 V (82.54%) | 208008.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 125.1 V (31.27%) | 274.9 V | 206.35 V (51.59%) | 130005.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 80.06 V (20.02%) | 319.9 V | 132.07 V (33.02%) | 83203.2 W | Drop High |
| 35 mm² | 125 A | 97 A | 57.19 V (14.3%) | 342.8 V | 94.33 V (23.58%) | 59430.9 W | Drop High |
| 50 mm² | 151 A | 118 A | 40.03 V (10.01%) | 360.0 V | 66.03 V (16.51%) | 41601.6 W | Drop High |
| 70 mm² | 192 A | 150 A | 28.59 V (7.15%) | 371.4 V | 47.17 V (11.79%) | 29715.4 W | Drop High |
| 95 mm² | 232 A | 181 A | 21.07 V (5.27%) | 378.9 V | 34.75 V (8.69%) | 21895.6 W | Drop High |
| 120 mm² | 269 A | 210 A | 16.68 V (4.17%) | 383.3 V | 27.51 V (6.88%) | 17334.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 13.34 V (3.34%) | 386.7 V | 22.01 V (5.5%) | 13867.2 W | Drop High |
| 185 mm² | 353 A | 275 A | 10.82 V (2.7%) | 389.2 V | 17.85 V (4.46%) | 11243.7 W | Drop High |
| 240 mm² | 415 A | 324 A | 8.34 V (2.08%) | 391.7 V | 13.76 V (3.44%) | 8667.0 W | Drop High |
| 300 mm² | 477 A | 372 A | 6.67 V (1.67%) | 393.3 V | 11.01 V (2.75%) | 6933.6 W | Drop High |
| 400 mm² | 570 A | 445 A | 5.0 V (1.25%) | 395.0 V | 8.25 V (2.06%) | 5200.2 W | Drop High |
FAQ — Kabeltværsnit for 600 Ampere ved 90 Meter (400V)
Hvilket kabeltværsnit kræves til 600A ved 90 meter (400V)?
Til 600 Ampere over 90 meter ved 400V anbefales 2× 400 mm² kobberkabel (spændingsfald 2.5V / 0.62%).
Hvor mange kW svarer 600A ved 400V til?
Det svarer til 415.69 kW med en anbefalet sikring på 600A.
Related Lengths & Currents (400V)
600A · 5m (400V)600A · 10m (400V)600A · 15m (400V)600A · 20m (400V)600A · 25m (400V)600A · 30m (400V)600A · 35m (400V)600A · 40m (400V)600A · 45m (400V)600A · 50m (400V)600A · 60m (400V)600A · 70m (400V)10A · 90m (400V)16A · 90m (400V)20A · 90m (400V)25A · 90m (400V)32A · 90m (400V)40A · 90m (400V)50A · 90m (400V)63A · 90m (400V)80A · 90m (400V)100A · 90m (400V)125A · 90m (400V)160A · 90m (400V)200A · 90m (400V)