Kabeltværsnit for 90 Ampere ved 150 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 90 A over 150 m ved 400V.
Copper Cable (≤3% Drop)50 mm²Drop: 10.01V (2.5%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 11.79V (2.95%)
Voltage at Load390.0 VLine Loss: 1560.1 W
Max Power & Breaker62.35 kW90A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 90A at 150m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 333.59 V (83.4%) | 66.4 V | 550.27 V (137.57%) | 52002.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 200.16 V (50.04%) | 199.8 V | 330.16 V (82.54%) | 31201.2 W | Drop High |
| 4 mm² | 32 A | 25 A | 125.1 V (31.27%) | 274.9 V | 206.35 V (51.59%) | 19500.8 W | Drop High |
| 6 mm² | 41 A | 32 A | 83.4 V (20.85%) | 316.6 V | 137.57 V (34.39%) | 13000.5 W | Drop High |
| 10 mm² | 57 A | 44 A | 50.04 V (12.51%) | 350.0 V | 82.54 V (20.64%) | 7800.3 W | Drop High |
| 16 mm² | 76 A | 59 A | 31.27 V (7.82%) | 368.7 V | 51.59 V (12.9%) | 4875.2 W | Drop High |
| 25 mm² | 101 A | 78 A | 20.02 V (5.0%) | 380.0 V | 33.02 V (8.25%) | 3120.1 W | Drop High |
| 35 mm² | 125 A | 97 A | 14.3 V (3.57%) | 385.7 V | 23.58 V (5.9%) | 2228.7 W | ~ ≤5% |
| 50 mm² | 151 A | 118 A | 10.01 V (2.5%) | 390.0 V | 16.51 V (4.13%) | 1560.1 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 7.15 V (1.79%) | 392.9 V | 11.79 V (2.95%) | 1114.3 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 5.27 V (1.32%) | 394.7 V | 8.69 V (2.17%) | 821.1 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 4.17 V (1.04%) | 395.8 V | 6.88 V (1.72%) | 650.0 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 3.34 V (0.83%) | 396.7 V | 5.5 V (1.38%) | 520.0 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 2.7 V (0.68%) | 397.3 V | 4.46 V (1.12%) | 421.6 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 2.08 V (0.52%) | 397.9 V | 3.44 V (0.86%) | 325.0 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 1.67 V (0.42%) | 398.3 V | 2.75 V (0.69%) | 260.0 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 1.25 V (0.31%) | 398.7 V | 2.06 V (0.52%) | 195.0 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 90 Ampere ved 150 Meter (400V)
Hvilket kabeltværsnit kræves til 90A ved 150 meter (400V)?
Til 90 Ampere over 150 meter ved 400V anbefales 50 mm² kobberkabel (spændingsfald 10.01V / 2.5%).
Hvor mange kW svarer 90A ved 400V til?
Det svarer til 62.35 kW med en anbefalet sikring på 90A.
Related Lengths & Currents (400V)
90A · 5m (400V)90A · 10m (400V)90A · 15m (400V)90A · 20m (400V)90A · 25m (400V)90A · 30m (400V)90A · 35m (400V)90A · 40m (400V)90A · 45m (400V)90A · 50m (400V)90A · 60m (400V)90A · 70m (400V)10A · 150m (400V)16A · 150m (400V)20A · 150m (400V)25A · 150m (400V)32A · 150m (400V)40A · 150m (400V)50A · 150m (400V)63A · 150m (400V)80A · 150m (400V)100A · 150m (400V)125A · 150m (400V)160A · 150m (400V)200A · 150m (400V)