Kabeltværsnit for 900 Ampere ved 90 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 900 A over 90 m ved 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 4.33V (1.89%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 14.3V (6.22%)
Voltage at Load225.7 VLine Loss: 3900.2 W
Max Power & Breaker207.0 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2311.2 V (1004.87%)0.0 V3812.4 V (1657.57%)2080080.0 WDrop High
2.5 mm²24 A18 A1386.72 V (602.92%)0.0 V2287.44 V (994.54%)1248048.0 WDrop High
4 mm²32 A25 A866.7 V (376.83%)0.0 V1429.65 V (621.59%)780030.0 WDrop High
6 mm²41 A32 A577.8 V (251.22%)0.0 V953.1 V (414.39%)520020.0 WDrop High
10 mm²57 A44 A346.68 V (150.73%)0.0 V571.86 V (248.63%)312012.0 WDrop High
16 mm²76 A59 A216.67 V (94.21%)13.3 V357.41 V (155.4%)195007.5 WDrop High
25 mm²101 A78 A138.67 V (60.29%)91.3 V228.74 V (99.45%)124804.8 WDrop High
35 mm²125 A97 A99.05 V (43.07%)130.9 V163.39 V (71.04%)89146.3 WDrop High
50 mm²151 A118 A69.34 V (30.15%)160.7 V114.37 V (49.73%)62402.4 WDrop High
70 mm²192 A150 A49.53 V (21.53%)180.5 V81.69 V (35.52%)44573.1 WDrop High
95 mm²232 A181 A36.49 V (15.87%)193.5 V60.2 V (26.17%)32843.4 WDrop High
120 mm²269 A210 A28.89 V (12.56%)201.1 V47.65 V (20.72%)26001.0 WDrop High
150 mm²309 A241 A23.11 V (10.05%)206.9 V38.12 V (16.58%)20800.8 WDrop High
185 mm²353 A275 A18.74 V (8.15%)211.3 V30.91 V (13.44%)16865.5 WDrop High
240 mm²415 A324 A14.44 V (6.28%)215.6 V23.83 V (10.36%)13000.5 WDrop High
300 mm²477 A372 A11.56 V (5.02%)218.4 V19.06 V (8.29%)10400.4 WDrop High
400 mm²570 A445 A8.67 V (3.77%)221.3 V14.3 V (6.22%)7800.3 WDrop High

FAQ — Kabeltværsnit for 900 Ampere ved 90 Meter (230V)

Hvilket kabeltværsnit kræves til 900A ved 90 meter (230V)?

Til 900 Ampere over 90 meter ved 230V anbefales 2× 400 mm² kobberkabel (spændingsfald 4.33V / 1.89%).

Hvor mange kW svarer 900A ved 230V til?

Det svarer til 207.0 kW med en anbefalet sikring på 1000A.