Kabelquerschnitt für 110 Ampere bei 120 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 110 A über 120 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)50 mm²Drop: 9.79V (2.45%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 11.53V (2.88%)
Voltage at Load390.2 VLine Loss: 1864.4 W
Max Power & Breaker76.21 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A326.18 V (81.54%)73.8 V538.04 V (134.51%)62145.6 WDrop High
2.5 mm²24 A18 A195.71 V (48.93%)204.3 V322.83 V (80.71%)37287.4 WDrop High
4 mm²32 A25 A122.32 V (30.58%)277.7 V201.77 V (50.44%)23304.6 WDrop High
6 mm²41 A32 A81.54 V (20.39%)318.5 V134.51 V (33.63%)15536.4 WDrop High
10 mm²57 A44 A48.93 V (12.23%)351.1 V80.71 V (20.18%)9321.8 WDrop High
16 mm²76 A59 A30.58 V (7.64%)369.4 V50.44 V (12.61%)5826.2 WDrop High
25 mm²101 A78 A19.57 V (4.89%)380.4 V32.28 V (8.07%)3728.7 WDrop High
35 mm²125 A97 A13.98 V (3.49%)386.0 V23.06 V (5.76%)2663.4 W~ ≤5%
50 mm²151 A118 A9.79 V (2.45%)390.2 V16.14 V (4.04%)1864.4 W✓ OK (≤3%)
70 mm²192 A150 A6.99 V (1.75%)393.0 V11.53 V (2.88%)1331.7 W✓ OK (≤3%)
95 mm²232 A181 A5.15 V (1.29%)394.8 V8.5 V (2.12%)981.2 W✓ OK (≤3%)
120 mm²269 A210 A4.08 V (1.02%)395.9 V6.73 V (1.68%)776.8 W✓ OK (≤3%)
150 mm²309 A241 A3.26 V (0.82%)396.7 V5.38 V (1.35%)621.5 W✓ OK (≤3%)
185 mm²353 A275 A2.64 V (0.66%)397.4 V4.36 V (1.09%)503.9 W✓ OK (≤3%)
240 mm²415 A324 A2.04 V (0.51%)398.0 V3.36 V (0.84%)388.4 W✓ OK (≤3%)
300 mm²477 A372 A1.63 V (0.41%)398.4 V2.69 V (0.67%)310.7 W✓ OK (≤3%)
400 mm²570 A445 A1.22 V (0.31%)398.8 V2.02 V (0.5%)233.0 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 110 Ampere bei 120 Meter (400V)

Welcher Kabelquerschnitt wird für 110A bei 120m (400V) benötigt?

Für 110 Ampere über 120 Meter bei 400V wird ein Kupferkabel von 50 mm² empfohlen, um den Spannungsfall unter 3% (9.79V bzw. 2.45%) zu halten.

Wie hoch ist die maximale Leistung bei 110A und 400V?

Die übertragbare Leistung beträgt 76.21 kW bei einer empfohlenen Absicherung von 110A.