Kabelquerschnitt für 110 Ampere bei 500 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 110 A über 500 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)185 mm²Drop: 11.02V (2.75%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 11.21V (2.8%)
Voltage at Load389.0 VLine Loss: 2099.5 W
Max Power & Breaker76.21 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1359.08 V (339.77%)0.0 V2241.85 V (560.46%)258940.0 WDrop High
2.5 mm²24 A18 A815.45 V (203.86%)0.0 V1345.11 V (336.28%)155364.0 WDrop High
4 mm²32 A25 A509.66 V (127.41%)0.0 V840.69 V (210.17%)97102.5 WDrop High
6 mm²41 A32 A339.77 V (84.94%)60.2 V560.46 V (140.12%)64735.0 WDrop High
10 mm²57 A44 A203.86 V (50.97%)196.1 V336.28 V (84.07%)38841.0 WDrop High
16 mm²76 A59 A127.41 V (31.85%)272.6 V210.17 V (52.54%)24275.6 WDrop High
25 mm²101 A78 A81.54 V (20.39%)318.5 V134.51 V (33.63%)15536.4 WDrop High
35 mm²125 A97 A58.25 V (14.56%)341.8 V96.08 V (24.02%)11097.4 WDrop High
50 mm²151 A118 A40.77 V (10.19%)359.2 V67.26 V (16.81%)7768.2 WDrop High
70 mm²192 A150 A29.12 V (7.28%)370.9 V48.04 V (12.01%)5548.7 WDrop High
95 mm²232 A181 A21.46 V (5.36%)378.5 V35.4 V (8.85%)4088.5 WDrop High
120 mm²269 A210 A16.99 V (4.25%)383.0 V28.02 V (7.01%)3236.7 W~ ≤5%
150 mm²309 A241 A13.59 V (3.4%)386.4 V22.42 V (5.6%)2589.4 W~ ≤5%
185 mm²353 A275 A11.02 V (2.75%)389.0 V18.18 V (4.54%)2099.5 W✓ OK (≤3%)
240 mm²415 A324 A8.49 V (2.12%)391.5 V14.01 V (3.5%)1618.4 W✓ OK (≤3%)
300 mm²477 A372 A6.8 V (1.7%)393.2 V11.21 V (2.8%)1294.7 W✓ OK (≤3%)
400 mm²570 A445 A5.1 V (1.27%)394.9 V8.41 V (2.1%)971.0 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 110 Ampere bei 500 Meter (400V)

Welcher Kabelquerschnitt wird für 110A bei 500m (400V) benötigt?

Für 110 Ampere über 500 Meter bei 400V wird ein Kupferkabel von 185 mm² empfohlen, um den Spannungsfall unter 3% (11.02V bzw. 2.75%) zu halten.

Wie hoch ist die maximale Leistung bei 110A und 400V?

Die übertragbare Leistung beträgt 76.21 kW bei einer empfohlenen Absicherung von 110A.