Kabelquerschnitt für 125 Ampere bei 20 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 125 A über 20 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 2.65V (0.66%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 2.18V (0.55%)
Voltage at Load397.4 VLine Loss: 573.2 W
Max Power & Breaker86.6 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A61.78 V (15.44%)338.2 V101.9 V (25.48%)13375.0 WDrop High
2.5 mm²24 A18 A37.07 V (9.27%)362.9 V61.14 V (15.29%)8025.0 WDrop High
4 mm²32 A25 A23.17 V (5.79%)376.8 V38.21 V (9.55%)5015.6 WDrop High
6 mm²41 A32 A15.44 V (3.86%)384.6 V25.48 V (6.37%)3343.8 WDrop High
10 mm²57 A44 A9.27 V (2.32%)390.7 V15.29 V (3.82%)2006.2 WDrop High
16 mm²76 A59 A5.79 V (1.45%)394.2 V9.55 V (2.39%)1253.9 WDrop High
25 mm²101 A78 A3.71 V (0.93%)396.3 V6.11 V (1.53%)802.5 WDrop High
35 mm²125 A97 A2.65 V (0.66%)397.4 V4.37 V (1.09%)573.2 W✓ OK (≤3%)
50 mm²151 A118 A1.85 V (0.46%)398.1 V3.06 V (0.76%)401.2 W✓ OK (≤3%)
70 mm²192 A150 A1.32 V (0.33%)398.7 V2.18 V (0.55%)286.6 W✓ OK (≤3%)
95 mm²232 A181 A0.98 V (0.24%)399.0 V1.61 V (0.4%)211.2 W✓ OK (≤3%)
120 mm²269 A210 A0.77 V (0.19%)399.2 V1.27 V (0.32%)167.2 W✓ OK (≤3%)
150 mm²309 A241 A0.62 V (0.15%)399.4 V1.02 V (0.25%)133.8 W✓ OK (≤3%)
185 mm²353 A275 A0.5 V (0.13%)399.5 V0.83 V (0.21%)108.4 W✓ OK (≤3%)
240 mm²415 A324 A0.39 V (0.1%)399.6 V0.64 V (0.16%)83.6 W✓ OK (≤3%)
300 mm²477 A372 A0.31 V (0.08%)399.7 V0.51 V (0.13%)66.9 W✓ OK (≤3%)
400 mm²570 A445 A0.23 V (0.06%)399.8 V0.38 V (0.1%)50.2 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 125 Ampere bei 20 Meter (400V)

Welcher Kabelquerschnitt wird für 125A bei 20m (400V) benötigt?

Für 125 Ampere über 20 Meter bei 400V wird ein Kupferkabel von 35 mm² empfohlen, um den Spannungsfall unter 3% (2.65V bzw. 0.66%) zu halten.

Wie hoch ist die maximale Leistung bei 125A und 400V?

Die übertragbare Leistung beträgt 86.6 kW bei einer empfohlenen Absicherung von 125A.