Kabelquerschnitt für 125 Ampere bei 5 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 125 A über 5 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 0.66V (0.17%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 0.55V (0.14%)
Voltage at Load399.3 VLine Loss: 143.3 W
Max Power & Breaker86.6 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A15.44 V (3.86%)384.6 V25.48 V (6.37%)3343.8 WDrop High
2.5 mm²24 A18 A9.27 V (2.32%)390.7 V15.29 V (3.82%)2006.2 WDrop High
4 mm²32 A25 A5.79 V (1.45%)394.2 V9.55 V (2.39%)1253.9 WDrop High
6 mm²41 A32 A3.86 V (0.97%)396.1 V6.37 V (1.59%)835.9 WDrop High
10 mm²57 A44 A2.32 V (0.58%)397.7 V3.82 V (0.96%)501.6 WDrop High
16 mm²76 A59 A1.45 V (0.36%)398.6 V2.39 V (0.6%)313.5 WDrop High
25 mm²101 A78 A0.93 V (0.23%)399.1 V1.53 V (0.38%)200.6 WDrop High
35 mm²125 A97 A0.66 V (0.17%)399.3 V1.09 V (0.27%)143.3 W✓ OK (≤3%)
50 mm²151 A118 A0.46 V (0.12%)399.5 V0.76 V (0.19%)100.3 W✓ OK (≤3%)
70 mm²192 A150 A0.33 V (0.08%)399.7 V0.55 V (0.14%)71.7 W✓ OK (≤3%)
95 mm²232 A181 A0.24 V (0.06%)399.8 V0.4 V (0.1%)52.8 W✓ OK (≤3%)
120 mm²269 A210 A0.19 V (0.05%)399.8 V0.32 V (0.08%)41.8 W✓ OK (≤3%)
150 mm²309 A241 A0.15 V (0.04%)399.8 V0.25 V (0.06%)33.4 W✓ OK (≤3%)
185 mm²353 A275 A0.13 V (0.03%)399.9 V0.21 V (0.05%)27.1 W✓ OK (≤3%)
240 mm²415 A324 A0.1 V (0.02%)399.9 V0.16 V (0.04%)20.9 W✓ OK (≤3%)
300 mm²477 A372 A0.08 V (0.02%)399.9 V0.13 V (0.03%)16.7 W✓ OK (≤3%)
400 mm²570 A445 A0.06 V (0.01%)399.9 V0.1 V (0.02%)12.5 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 125 Ampere bei 5 Meter (400V)

Welcher Kabelquerschnitt wird für 125A bei 5m (400V) benötigt?

Für 125 Ampere über 5 Meter bei 400V wird ein Kupferkabel von 35 mm² empfohlen, um den Spannungsfall unter 3% (0.66V bzw. 0.17%) zu halten.

Wie hoch ist die maximale Leistung bei 125A und 400V?

Die übertragbare Leistung beträgt 86.6 kW bei einer empfohlenen Absicherung von 125A.