Kabelquerschnitt für 125 Ampere bei 30 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 125 A über 30 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 3.97V (0.99%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 3.28V (0.82%)
Voltage at Load396.0 VLine Loss: 859.8 W
Max Power & Breaker86.6 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A92.66 V (23.17%)307.3 V152.85 V (38.21%)20062.5 WDrop High
2.5 mm²24 A18 A55.6 V (13.9%)344.4 V91.71 V (22.93%)12037.5 WDrop High
4 mm²32 A25 A34.75 V (8.69%)365.3 V57.32 V (14.33%)7523.4 WDrop High
6 mm²41 A32 A23.17 V (5.79%)376.8 V38.21 V (9.55%)5015.6 WDrop High
10 mm²57 A44 A13.9 V (3.47%)386.1 V22.93 V (5.73%)3009.4 WDrop High
16 mm²76 A59 A8.69 V (2.17%)391.3 V14.33 V (3.58%)1880.9 WDrop High
25 mm²101 A78 A5.56 V (1.39%)394.4 V9.17 V (2.29%)1203.8 WDrop High
35 mm²125 A97 A3.97 V (0.99%)396.0 V6.55 V (1.64%)859.8 W✓ OK (≤3%)
50 mm²151 A118 A2.78 V (0.69%)397.2 V4.59 V (1.15%)601.9 W✓ OK (≤3%)
70 mm²192 A150 A1.99 V (0.5%)398.0 V3.28 V (0.82%)429.9 W✓ OK (≤3%)
95 mm²232 A181 A1.46 V (0.37%)398.5 V2.41 V (0.6%)316.8 W✓ OK (≤3%)
120 mm²269 A210 A1.16 V (0.29%)398.8 V1.91 V (0.48%)250.8 W✓ OK (≤3%)
150 mm²309 A241 A0.93 V (0.23%)399.1 V1.53 V (0.38%)200.6 W✓ OK (≤3%)
185 mm²353 A275 A0.75 V (0.19%)399.2 V1.24 V (0.31%)162.7 W✓ OK (≤3%)
240 mm²415 A324 A0.58 V (0.14%)399.4 V0.96 V (0.24%)125.4 W✓ OK (≤3%)
300 mm²477 A372 A0.46 V (0.12%)399.5 V0.76 V (0.19%)100.3 W✓ OK (≤3%)
400 mm²570 A445 A0.35 V (0.09%)399.7 V0.57 V (0.14%)75.2 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 125 Ampere bei 30 Meter (400V)

Welcher Kabelquerschnitt wird für 125A bei 30m (400V) benötigt?

Für 125 Ampere über 30 Meter bei 400V wird ein Kupferkabel von 35 mm² empfohlen, um den Spannungsfall unter 3% (3.97V bzw. 0.99%) zu halten.

Wie hoch ist die maximale Leistung bei 125A und 400V?

Die übertragbare Leistung beträgt 86.6 kW bei einer empfohlenen Absicherung von 125A.