Kabelquerschnitt für 25 Ampere bei 30 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 25 A über 30 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)4 mm²Drop: 6.95V (1.74%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 11.46V (2.87%)
Voltage at Load393.1 VLine Loss: 300.9 W
Max Power & Breaker17.32 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A18.53 V (4.63%)381.5 V30.57 V (7.64%)802.5 WDrop High
2.5 mm²24 A18 A11.12 V (2.78%)388.9 V18.34 V (4.59%)481.5 WDrop High
4 mm²32 A25 A6.95 V (1.74%)393.1 V11.46 V (2.87%)300.9 W✓ OK (≤3%)
6 mm²41 A32 A4.63 V (1.16%)395.4 V7.64 V (1.91%)200.6 W✓ OK (≤3%)
10 mm²57 A44 A2.78 V (0.69%)397.2 V4.59 V (1.15%)120.4 W✓ OK (≤3%)
16 mm²76 A59 A1.74 V (0.43%)398.3 V2.87 V (0.72%)75.2 W✓ OK (≤3%)
25 mm²101 A78 A1.11 V (0.28%)398.9 V1.83 V (0.46%)48.2 W✓ OK (≤3%)
35 mm²125 A97 A0.79 V (0.2%)399.2 V1.31 V (0.33%)34.4 W✓ OK (≤3%)
50 mm²151 A118 A0.56 V (0.14%)399.4 V0.92 V (0.23%)24.1 W✓ OK (≤3%)
70 mm²192 A150 A0.4 V (0.1%)399.6 V0.66 V (0.16%)17.2 W✓ OK (≤3%)
95 mm²232 A181 A0.29 V (0.07%)399.7 V0.48 V (0.12%)12.7 W✓ OK (≤3%)
120 mm²269 A210 A0.23 V (0.06%)399.8 V0.38 V (0.1%)10.0 W✓ OK (≤3%)
150 mm²309 A241 A0.19 V (0.05%)399.8 V0.31 V (0.08%)8.0 W✓ OK (≤3%)
185 mm²353 A275 A0.15 V (0.04%)399.8 V0.25 V (0.06%)6.5 W✓ OK (≤3%)
240 mm²415 A324 A0.12 V (0.03%)399.9 V0.19 V (0.05%)5.0 W✓ OK (≤3%)
300 mm²477 A372 A0.09 V (0.02%)399.9 V0.15 V (0.04%)4.0 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.02%)399.9 V0.11 V (0.03%)3.0 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 25 Ampere bei 30 Meter (400V)

Welcher Kabelquerschnitt wird für 25A bei 30m (400V) benötigt?

Für 25 Ampere über 30 Meter bei 400V wird ein Kupferkabel von 4 mm² empfohlen, um den Spannungsfall unter 3% (6.95V bzw. 1.74%) zu halten.

Wie hoch ist die maximale Leistung bei 25A und 400V?

Die übertragbare Leistung beträgt 17.32 kW bei einer empfohlenen Absicherung von 25A.