Kabelquerschnitt für 175 Ampere bei 25 Meter (230V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 175 A über 25 m einfache Leitungslänge bei 230V.

Copper Cable (≤3% Drop)70 mm²Drop: 2.67V (1.16%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 3.25V (1.41%)
Voltage at Load227.3 VLine Loss: 468.1 W
Max Power & Breaker40.25 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A124.83 V (54.28%)105.2 V205.92 V (89.53%)21845.8 WDrop High
2.5 mm²24 A18 A74.9 V (32.57%)155.1 V123.55 V (53.72%)13107.5 WDrop High
4 mm²32 A25 A46.81 V (20.35%)183.2 V77.22 V (33.57%)8192.2 WDrop High
6 mm²41 A32 A31.21 V (13.57%)198.8 V51.48 V (22.38%)5461.5 WDrop High
10 mm²57 A44 A18.72 V (8.14%)211.3 V30.89 V (13.43%)3276.9 WDrop High
16 mm²76 A59 A11.7 V (5.09%)218.3 V19.3 V (8.39%)2048.0 WDrop High
25 mm²101 A78 A7.49 V (3.26%)222.5 V12.35 V (5.37%)1310.7 WDrop High
35 mm²125 A97 A5.35 V (2.33%)224.7 V8.82 V (3.84%)936.2 WDrop High
50 mm²151 A118 A3.74 V (1.63%)226.3 V6.18 V (2.69%)655.4 WDrop High
70 mm²192 A150 A2.67 V (1.16%)227.3 V4.41 V (1.92%)468.1 W✓ OK (≤3%)
95 mm²232 A181 A1.97 V (0.86%)228.0 V3.25 V (1.41%)344.9 W✓ OK (≤3%)
120 mm²269 A210 A1.56 V (0.68%)228.4 V2.57 V (1.12%)273.1 W✓ OK (≤3%)
150 mm²309 A241 A1.25 V (0.54%)228.8 V2.06 V (0.9%)218.5 W✓ OK (≤3%)
185 mm²353 A275 A1.01 V (0.44%)229.0 V1.67 V (0.73%)177.1 W✓ OK (≤3%)
240 mm²415 A324 A0.78 V (0.34%)229.2 V1.29 V (0.56%)136.5 W✓ OK (≤3%)
300 mm²477 A372 A0.62 V (0.27%)229.4 V1.03 V (0.45%)109.2 W✓ OK (≤3%)
400 mm²570 A445 A0.47 V (0.2%)229.5 V0.77 V (0.34%)81.9 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 175 Ampere bei 25 Meter (230V)

Welcher Kabelquerschnitt wird für 175A bei 25m (230V) benötigt?

Für 175 Ampere über 25 Meter bei 230V wird ein Kupferkabel von 70 mm² empfohlen, um den Spannungsfall unter 3% (2.67V bzw. 1.16%) zu halten.

Wie hoch ist die maximale Leistung bei 175A und 230V?

Die übertragbare Leistung beträgt 40.25 kW bei einer empfohlenen Absicherung von 175A.