Kabelquerschnitt für 175 Ampere bei 35 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 175 A über 35 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 3.24V (0.81%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 3.94V (0.99%)
Voltage at Load396.8 VLine Loss: 983.1 W
Max Power & Breaker121.24 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A151.35 V (37.84%)248.6 V249.66 V (62.42%)45876.2 WDrop High
2.5 mm²24 A18 A90.81 V (22.7%)309.2 V149.8 V (37.45%)27525.7 WDrop High
4 mm²32 A25 A56.76 V (14.19%)343.2 V93.62 V (23.41%)17203.6 WDrop High
6 mm²41 A32 A37.84 V (9.46%)362.2 V62.42 V (15.6%)11469.1 WDrop High
10 mm²57 A44 A22.7 V (5.68%)377.3 V37.45 V (9.36%)6881.4 WDrop High
16 mm²76 A59 A14.19 V (3.55%)385.8 V23.41 V (5.85%)4300.9 WDrop High
25 mm²101 A78 A9.08 V (2.27%)390.9 V14.98 V (3.74%)2752.6 WDrop High
35 mm²125 A97 A6.49 V (1.62%)393.5 V10.7 V (2.67%)1966.1 WDrop High
50 mm²151 A118 A4.54 V (1.14%)395.5 V7.49 V (1.87%)1376.3 WDrop High
70 mm²192 A150 A3.24 V (0.81%)396.8 V5.35 V (1.34%)983.1 W✓ OK (≤3%)
95 mm²232 A181 A2.39 V (0.6%)397.6 V3.94 V (0.99%)724.4 W✓ OK (≤3%)
120 mm²269 A210 A1.89 V (0.47%)398.1 V3.12 V (0.78%)573.5 W✓ OK (≤3%)
150 mm²309 A241 A1.51 V (0.38%)398.5 V2.5 V (0.62%)458.8 W✓ OK (≤3%)
185 mm²353 A275 A1.23 V (0.31%)398.8 V2.02 V (0.51%)372.0 W✓ OK (≤3%)
240 mm²415 A324 A0.95 V (0.24%)399.1 V1.56 V (0.39%)286.7 W✓ OK (≤3%)
300 mm²477 A372 A0.76 V (0.19%)399.2 V1.25 V (0.31%)229.4 W✓ OK (≤3%)
400 mm²570 A445 A0.57 V (0.14%)399.4 V0.94 V (0.23%)172.0 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 175 Ampere bei 35 Meter (400V)

Welcher Kabelquerschnitt wird für 175A bei 35m (400V) benötigt?

Für 175 Ampere über 35 Meter bei 400V wird ein Kupferkabel von 70 mm² empfohlen, um den Spannungsfall unter 3% (3.24V bzw. 0.81%) zu halten.

Wie hoch ist die maximale Leistung bei 175A und 400V?

Die übertragbare Leistung beträgt 121.24 kW bei einer empfohlenen Absicherung von 175A.