Kabelquerschnitt für 25 Ampere bei 35 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 25 A über 35 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)4 mm²Drop: 8.11V (2.03%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 8.92V (2.23%)
Voltage at Load391.9 VLine Loss: 351.1 W
Max Power & Breaker17.32 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A21.62 V (5.41%)378.4 V35.67 V (8.92%)936.2 WDrop High
2.5 mm²24 A18 A12.97 V (3.24%)387.0 V21.4 V (5.35%)561.8 WDrop High
4 mm²32 A25 A8.11 V (2.03%)391.9 V13.37 V (3.34%)351.1 W✓ OK (≤3%)
6 mm²41 A32 A5.41 V (1.35%)394.6 V8.92 V (2.23%)234.1 W✓ OK (≤3%)
10 mm²57 A44 A3.24 V (0.81%)396.8 V5.35 V (1.34%)140.4 W✓ OK (≤3%)
16 mm²76 A59 A2.03 V (0.51%)398.0 V3.34 V (0.84%)87.8 W✓ OK (≤3%)
25 mm²101 A78 A1.3 V (0.32%)398.7 V2.14 V (0.53%)56.2 W✓ OK (≤3%)
35 mm²125 A97 A0.93 V (0.23%)399.1 V1.53 V (0.38%)40.1 W✓ OK (≤3%)
50 mm²151 A118 A0.65 V (0.16%)399.4 V1.07 V (0.27%)28.1 W✓ OK (≤3%)
70 mm²192 A150 A0.46 V (0.12%)399.5 V0.76 V (0.19%)20.1 W✓ OK (≤3%)
95 mm²232 A181 A0.34 V (0.09%)399.7 V0.56 V (0.14%)14.8 W✓ OK (≤3%)
120 mm²269 A210 A0.27 V (0.07%)399.7 V0.45 V (0.11%)11.7 W✓ OK (≤3%)
150 mm²309 A241 A0.22 V (0.05%)399.8 V0.36 V (0.09%)9.4 W✓ OK (≤3%)
185 mm²353 A275 A0.18 V (0.04%)399.8 V0.29 V (0.07%)7.6 W✓ OK (≤3%)
240 mm²415 A324 A0.14 V (0.03%)399.9 V0.22 V (0.06%)5.9 W✓ OK (≤3%)
300 mm²477 A372 A0.11 V (0.03%)399.9 V0.18 V (0.04%)4.7 W✓ OK (≤3%)
400 mm²570 A445 A0.08 V (0.02%)399.9 V0.13 V (0.03%)3.5 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 25 Ampere bei 35 Meter (400V)

Welcher Kabelquerschnitt wird für 25A bei 35m (400V) benötigt?

Für 25 Ampere über 35 Meter bei 400V wird ein Kupferkabel von 4 mm² empfohlen, um den Spannungsfall unter 3% (8.11V bzw. 2.03%) zu halten.

Wie hoch ist die maximale Leistung bei 25A und 400V?

Die übertragbare Leistung beträgt 17.32 kW bei einer empfohlenen Absicherung von 25A.