Kabelquerschnitt für 175 Ampere bei 60 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 175 A über 60 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 5.56V (1.39%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 6.76V (1.69%)
Voltage at Load394.4 VLine Loss: 1685.2 W
Max Power & Breaker121.24 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A259.46 V (64.87%)140.5 V427.99 V (107.0%)78645.0 WDrop High
2.5 mm²24 A18 A155.68 V (38.92%)244.3 V256.79 V (64.2%)47187.0 WDrop High
4 mm²32 A25 A97.3 V (24.32%)302.7 V160.5 V (40.12%)29491.9 WDrop High
6 mm²41 A32 A64.87 V (16.22%)335.1 V107.0 V (26.75%)19661.2 WDrop High
10 mm²57 A44 A38.92 V (9.73%)361.1 V64.2 V (16.05%)11796.8 WDrop High
16 mm²76 A59 A24.32 V (6.08%)375.7 V40.12 V (10.03%)7373.0 WDrop High
25 mm²101 A78 A15.57 V (3.89%)384.4 V25.68 V (6.42%)4718.7 WDrop High
35 mm²125 A97 A11.12 V (2.78%)388.9 V18.34 V (4.59%)3370.5 WDrop High
50 mm²151 A118 A7.78 V (1.95%)392.2 V12.84 V (3.21%)2359.3 WDrop High
70 mm²192 A150 A5.56 V (1.39%)394.4 V9.17 V (2.29%)1685.2 W✓ OK (≤3%)
95 mm²232 A181 A4.1 V (1.02%)395.9 V6.76 V (1.69%)1241.8 W✓ OK (≤3%)
120 mm²269 A210 A3.24 V (0.81%)396.8 V5.35 V (1.34%)983.1 W✓ OK (≤3%)
150 mm²309 A241 A2.59 V (0.65%)397.4 V4.28 V (1.07%)786.5 W✓ OK (≤3%)
185 mm²353 A275 A2.1 V (0.53%)397.9 V3.47 V (0.87%)637.7 W✓ OK (≤3%)
240 mm²415 A324 A1.62 V (0.41%)398.4 V2.67 V (0.67%)491.5 W✓ OK (≤3%)
300 mm²477 A372 A1.3 V (0.32%)398.7 V2.14 V (0.53%)393.2 W✓ OK (≤3%)
400 mm²570 A445 A0.97 V (0.24%)399.0 V1.6 V (0.4%)294.9 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 175 Ampere bei 60 Meter (400V)

Welcher Kabelquerschnitt wird für 175A bei 60m (400V) benötigt?

Für 175 Ampere über 60 Meter bei 400V wird ein Kupferkabel von 70 mm² empfohlen, um den Spannungsfall unter 3% (5.56V bzw. 1.39%) zu halten.

Wie hoch ist die maximale Leistung bei 175A und 400V?

Die übertragbare Leistung beträgt 121.24 kW bei einer empfohlenen Absicherung von 175A.