⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 175 Ampere bei 400 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 175 A über 400 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)240 mm²Drop: 10.81V (2.7%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 10.7V (2.67%)
Voltage at Load389.2 VLine Loss: 3276.9 W
Max Power & Breaker121.24 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1729.74 V (432.44%)0.0 V2853.27 V (713.32%)524300.0 WDrop High
2.5 mm²24 A18 A1037.84 V (259.46%)0.0 V1711.96 V (427.99%)314580.0 WDrop High
4 mm²32 A25 A648.65 V (162.16%)0.0 V1069.97 V (267.49%)196612.5 WDrop High
6 mm²41 A32 A432.44 V (108.11%)0.0 V713.32 V (178.33%)131075.0 WDrop High
10 mm²57 A44 A259.46 V (64.87%)140.5 V427.99 V (107.0%)78645.0 WDrop High
16 mm²76 A59 A162.16 V (40.54%)237.8 V267.49 V (66.87%)49153.1 WDrop High
25 mm²101 A78 A103.78 V (25.95%)296.2 V171.2 V (42.8%)31458.0 WDrop High
35 mm²125 A97 A74.13 V (18.53%)325.9 V122.28 V (30.57%)22470.0 WDrop High
50 mm²151 A118 A51.89 V (12.97%)348.1 V85.6 V (21.4%)15729.0 WDrop High
70 mm²192 A150 A37.07 V (9.27%)362.9 V61.14 V (15.29%)11235.0 WDrop High
95 mm²232 A181 A27.31 V (6.83%)372.7 V45.05 V (11.26%)8278.4 WDrop High
120 mm²269 A210 A21.62 V (5.41%)378.4 V35.67 V (8.92%)6553.7 WDrop High
150 mm²309 A241 A17.3 V (4.32%)382.7 V28.53 V (7.13%)5243.0 W~ ≤5%
185 mm²353 A275 A14.02 V (3.51%)386.0 V23.13 V (5.78%)4251.1 W~ ≤5%
240 mm²415 A324 A10.81 V (2.7%)389.2 V17.83 V (4.46%)3276.9 W✓ OK (≤3%)
300 mm²477 A372 A8.65 V (2.16%)391.4 V14.27 V (3.57%)2621.5 W✓ OK (≤3%)
400 mm²570 A445 A6.49 V (1.62%)393.5 V10.7 V (2.67%)1966.1 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 175 Ampere bei 400 Meter (400V)

Welcher Kabelquerschnitt wird für 175A bei 400m (400V) benötigt?

Für 175 Ampere über 400 Meter bei 400V wird ein Kupferkabel von 240 mm² empfohlen, um den Spannungsfall unter 3% (10.81V bzw. 2.7%) zu halten.

Wie hoch ist die maximale Leistung bei 175A und 400V?

Die übertragbare Leistung beträgt 121.24 kW bei einer empfohlenen Absicherung von 175A.