Kabelquerschnitt für 250 Ampere bei 250 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 250 A über 250 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)240 mm²Drop: 9.65V (2.41%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.55V (2.39%)
Voltage at Load390.3 VLine Loss: 4179.7 W
Max Power & Breaker173.21 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1544.41 V (386.1%)0.0 V2547.56 V (636.89%)668750.0 WDrop High
2.5 mm²24 A18 A926.65 V (231.66%)0.0 V1528.53 V (382.13%)401250.0 WDrop High
4 mm²32 A25 A579.15 V (144.79%)0.0 V955.33 V (238.83%)250781.2 WDrop High
6 mm²41 A32 A386.1 V (96.53%)13.9 V636.89 V (159.22%)167187.5 WDrop High
10 mm²57 A44 A231.66 V (57.92%)168.3 V382.13 V (95.53%)100312.5 WDrop High
16 mm²76 A59 A144.79 V (36.2%)255.2 V238.83 V (59.71%)62695.3 WDrop High
25 mm²101 A78 A92.66 V (23.17%)307.3 V152.85 V (38.21%)40125.0 WDrop High
35 mm²125 A97 A66.19 V (16.55%)333.8 V109.18 V (27.3%)28660.7 WDrop High
50 mm²151 A118 A46.33 V (11.58%)353.7 V76.43 V (19.11%)20062.5 WDrop High
70 mm²192 A150 A33.09 V (8.27%)366.9 V54.59 V (13.65%)14330.4 WDrop High
95 mm²232 A181 A24.39 V (6.1%)375.6 V40.22 V (10.06%)10559.2 WDrop High
120 mm²269 A210 A19.31 V (4.83%)380.7 V31.84 V (7.96%)8359.4 W~ ≤5%
150 mm²309 A241 A15.44 V (3.86%)384.6 V25.48 V (6.37%)6687.5 W~ ≤5%
185 mm²353 A275 A12.52 V (3.13%)387.5 V20.66 V (5.16%)5422.3 W~ ≤5%
240 mm²415 A324 A9.65 V (2.41%)390.3 V15.92 V (3.98%)4179.7 W✓ OK (≤3%)
300 mm²477 A372 A7.72 V (1.93%)392.3 V12.74 V (3.18%)3343.8 W✓ OK (≤3%)
400 mm²570 A445 A5.79 V (1.45%)394.2 V9.55 V (2.39%)2507.8 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 250 Ampere bei 250 Meter (400V)

Welcher Kabelquerschnitt wird für 250A bei 250m (400V) benötigt?

Für 250 Ampere über 250 Meter bei 400V wird ein Kupferkabel von 240 mm² empfohlen, um den Spannungsfall unter 3% (9.65V bzw. 2.41%) zu halten.

Wie hoch ist die maximale Leistung bei 250A und 400V?

Die übertragbare Leistung beträgt 173.21 kW bei einer empfohlenen Absicherung von 250A.