⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 275 Ampere bei 120 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 275 A über 120 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)150 mm²Drop: 8.15V (2.04%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 10.91V (2.73%)
Voltage at Load391.8 VLine Loss: 3884.1 W
Max Power & Breaker190.53 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 275A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A815.45 V (203.86%)0.0 V1345.11 V (336.28%)388410.0 WDrop High
2.5 mm²24 A18 A489.27 V (122.32%)0.0 V807.07 V (201.77%)233046.0 WDrop High
4 mm²32 A25 A305.79 V (76.45%)94.2 V504.42 V (126.1%)145653.8 WDrop High
6 mm²41 A32 A203.86 V (50.97%)196.1 V336.28 V (84.07%)97102.5 WDrop High
10 mm²57 A44 A122.32 V (30.58%)277.7 V201.77 V (50.44%)58261.5 WDrop High
16 mm²76 A59 A76.45 V (19.11%)323.6 V126.1 V (31.53%)36413.4 WDrop High
25 mm²101 A78 A48.93 V (12.23%)351.1 V80.71 V (20.18%)23304.6 WDrop High
35 mm²125 A97 A34.95 V (8.74%)365.1 V57.65 V (14.41%)16646.1 WDrop High
50 mm²151 A118 A24.46 V (6.12%)375.5 V40.35 V (10.09%)11652.3 WDrop High
70 mm²192 A150 A17.47 V (4.37%)382.5 V28.82 V (7.21%)8323.1 WDrop High
95 mm²232 A181 A12.88 V (3.22%)387.1 V21.24 V (5.31%)6132.8 WDrop High
120 mm²269 A210 A10.19 V (2.55%)389.8 V16.81 V (4.2%)4855.1 WDrop High
150 mm²309 A241 A8.15 V (2.04%)391.8 V13.45 V (3.36%)3884.1 W✓ OK (≤3%)
185 mm²353 A275 A6.61 V (1.65%)393.4 V10.91 V (2.73%)3149.3 W✓ OK (≤3%)
240 mm²415 A324 A5.1 V (1.27%)394.9 V8.41 V (2.1%)2427.6 W✓ OK (≤3%)
300 mm²477 A372 A4.08 V (1.02%)395.9 V6.73 V (1.68%)1942.0 W✓ OK (≤3%)
400 mm²570 A445 A3.06 V (0.76%)396.9 V5.04 V (1.26%)1456.5 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 275 Ampere bei 120 Meter (400V)

Welcher Kabelquerschnitt wird für 275A bei 120m (400V) benötigt?

Für 275 Ampere über 120 Meter bei 400V wird ein Kupferkabel von 150 mm² empfohlen, um den Spannungsfall unter 3% (8.15V bzw. 2.04%) zu halten.

Wie hoch ist die maximale Leistung bei 275A und 400V?

Die übertragbare Leistung beträgt 190.53 kW bei einer empfohlenen Absicherung von 300A.