Kabelquerschnitt für 300 Ampere bei 120 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 300 A über 120 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)150 mm²Drop: 8.9V (2.22%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 9.17V (2.29%)
Voltage at Load391.1 VLine Loss: 4622.4 W
Max Power & Breaker207.85 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A889.58 V (222.4%)0.0 V1467.39 V (366.85%)462240.0 WDrop High
2.5 mm²24 A18 A533.75 V (133.44%)0.0 V880.44 V (220.11%)277344.0 WDrop High
4 mm²32 A25 A333.59 V (83.4%)66.4 V550.27 V (137.57%)173340.0 WDrop High
6 mm²41 A32 A222.4 V (55.6%)177.6 V366.85 V (91.71%)115560.0 WDrop High
10 mm²57 A44 A133.44 V (33.36%)266.6 V220.11 V (55.03%)69336.0 WDrop High
16 mm²76 A59 A83.4 V (20.85%)316.6 V137.57 V (34.39%)43335.0 WDrop High
25 mm²101 A78 A53.37 V (13.34%)346.6 V88.04 V (22.01%)27734.4 WDrop High
35 mm²125 A97 A38.12 V (9.53%)361.9 V62.89 V (15.72%)19810.3 WDrop High
50 mm²151 A118 A26.69 V (6.67%)373.3 V44.02 V (11.01%)13867.2 WDrop High
70 mm²192 A150 A19.06 V (4.77%)380.9 V31.44 V (7.86%)9905.1 WDrop High
95 mm²232 A181 A14.05 V (3.51%)386.0 V23.17 V (5.79%)7298.5 WDrop High
120 mm²269 A210 A11.12 V (2.78%)388.9 V18.34 V (4.59%)5778.0 WDrop High
150 mm²309 A241 A8.9 V (2.22%)391.1 V14.67 V (3.67%)4622.4 W✓ OK (≤3%)
185 mm²353 A275 A7.21 V (1.8%)392.8 V11.9 V (2.97%)3747.9 W✓ OK (≤3%)
240 mm²415 A324 A5.56 V (1.39%)394.4 V9.17 V (2.29%)2889.0 W✓ OK (≤3%)
300 mm²477 A372 A4.45 V (1.11%)395.6 V7.34 V (1.83%)2311.2 W✓ OK (≤3%)
400 mm²570 A445 A3.34 V (0.83%)396.7 V5.5 V (1.38%)1733.4 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 300 Ampere bei 120 Meter (400V)

Welcher Kabelquerschnitt wird für 300A bei 120m (400V) benötigt?

Für 300 Ampere über 120 Meter bei 400V wird ein Kupferkabel von 150 mm² empfohlen, um den Spannungsfall unter 3% (8.9V bzw. 2.22%) zu halten.

Wie hoch ist die maximale Leistung bei 300A und 400V?

Die übertragbare Leistung beträgt 207.85 kW bei einer empfohlenen Absicherung von 300A.