Kabelquerschnitt für 425 Ampere bei 500 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 425 A über 500 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 9.85V (2.46%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 32.48V (8.12%)
Voltage at Load390.1 VLine Loss: 7247.6 W
Max Power & Breaker294.45 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5251.0 V (1312.75%)0.0 V8661.7 V (2165.42%)3865375.0 WDrop High
2.5 mm²24 A18 A3150.6 V (787.65%)0.0 V5197.02 V (1299.25%)2319225.0 WDrop High
4 mm²32 A25 A1969.13 V (492.28%)0.0 V3248.14 V (812.03%)1449515.6 WDrop High
6 mm²41 A32 A1312.75 V (328.19%)0.0 V2165.42 V (541.36%)966343.7 WDrop High
10 mm²57 A44 A787.65 V (196.91%)0.0 V1299.25 V (324.81%)579806.2 WDrop High
16 mm²76 A59 A492.28 V (123.07%)0.0 V812.03 V (203.01%)362378.9 WDrop High
25 mm²101 A78 A315.06 V (78.77%)84.9 V519.7 V (129.93%)231922.5 WDrop High
35 mm²125 A97 A225.04 V (56.26%)175.0 V371.22 V (92.8%)165658.9 WDrop High
50 mm²151 A118 A157.53 V (39.38%)242.5 V259.85 V (64.96%)115961.2 WDrop High
70 mm²192 A150 A112.52 V (28.13%)287.5 V185.61 V (46.4%)82829.5 WDrop High
95 mm²232 A181 A82.91 V (20.73%)317.1 V136.76 V (34.19%)61032.2 WDrop High
120 mm²269 A210 A65.64 V (16.41%)334.4 V108.27 V (27.07%)48317.2 WDrop High
150 mm²309 A241 A52.51 V (13.13%)347.5 V86.62 V (21.65%)38653.8 WDrop High
185 mm²353 A275 A42.58 V (10.64%)357.4 V70.23 V (17.56%)31340.9 WDrop High
240 mm²415 A324 A32.82 V (8.2%)367.2 V54.14 V (13.53%)24158.6 WDrop High
300 mm²477 A372 A26.26 V (6.56%)373.7 V43.31 V (10.83%)19326.9 WDrop High
400 mm²570 A445 A19.69 V (4.92%)380.3 V32.48 V (8.12%)14495.2 W~ ≤5%

FAQ — Kabelquerschnitt für 425 Ampere bei 500 Meter (400V)

Welcher Kabelquerschnitt wird für 425A bei 500m (400V) benötigt?

Für 425 Ampere über 500 Meter bei 400V wird ein Kupferkabel von 2× 400 mm² empfohlen, um den Spannungsfall unter 3% (9.85V bzw. 2.46%) zu halten.

Wie hoch ist die maximale Leistung bei 425A und 400V?

Die übertragbare Leistung beträgt 294.45 kW bei einer empfohlenen Absicherung von 450A.