⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 45 Ampere bei 200 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 45 A über 200 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 9.53V (2.38%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 11.01V (2.75%)
Voltage at Load390.5 VLine Loss: 742.9 W
Max Power & Breaker31.18 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A222.4 V (55.6%)177.6 V366.85 V (91.71%)17334.0 WDrop High
2.5 mm²24 A18 A133.44 V (33.36%)266.6 V220.11 V (55.03%)10400.4 WDrop High
4 mm²32 A25 A83.4 V (20.85%)316.6 V137.57 V (34.39%)6500.2 WDrop High
6 mm²41 A32 A55.6 V (13.9%)344.4 V91.71 V (22.93%)4333.5 WDrop High
10 mm²57 A44 A33.36 V (8.34%)366.6 V55.03 V (13.76%)2600.1 WDrop High
16 mm²76 A59 A20.85 V (5.21%)379.2 V34.39 V (8.6%)1625.1 WDrop High
25 mm²101 A78 A13.34 V (3.34%)386.7 V22.01 V (5.5%)1040.0 W~ ≤5%
35 mm²125 A97 A9.53 V (2.38%)390.5 V15.72 V (3.93%)742.9 W✓ OK (≤3%)
50 mm²151 A118 A6.67 V (1.67%)393.3 V11.01 V (2.75%)520.0 W✓ OK (≤3%)
70 mm²192 A150 A4.77 V (1.19%)395.2 V7.86 V (1.97%)371.4 W✓ OK (≤3%)
95 mm²232 A181 A3.51 V (0.88%)396.5 V5.79 V (1.45%)273.7 W✓ OK (≤3%)
120 mm²269 A210 A2.78 V (0.69%)397.2 V4.59 V (1.15%)216.7 W✓ OK (≤3%)
150 mm²309 A241 A2.22 V (0.56%)397.8 V3.67 V (0.92%)173.3 W✓ OK (≤3%)
185 mm²353 A275 A1.8 V (0.45%)398.2 V2.97 V (0.74%)140.5 W✓ OK (≤3%)
240 mm²415 A324 A1.39 V (0.35%)398.6 V2.29 V (0.57%)108.3 W✓ OK (≤3%)
300 mm²477 A372 A1.11 V (0.28%)398.9 V1.83 V (0.46%)86.7 W✓ OK (≤3%)
400 mm²570 A445 A0.83 V (0.21%)399.2 V1.38 V (0.34%)65.0 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 45 Ampere bei 200 Meter (400V)

Welcher Kabelquerschnitt wird für 45A bei 200m (400V) benötigt?

Für 45 Ampere über 200 Meter bei 400V wird ein Kupferkabel von 35 mm² empfohlen, um den Spannungsfall unter 3% (9.53V bzw. 2.38%) zu halten.

Wie hoch ist die maximale Leistung bei 45A und 400V?

Die übertragbare Leistung beträgt 31.18 kW bei einer empfohlenen Absicherung von 45A.