⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 45 Ampere bei 30 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 45 A über 30 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)10 mm²Drop: 5.0V (1.25%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 5.16V (1.29%)
Voltage at Load395.0 VLine Loss: 390.0 W
Max Power & Breaker31.18 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A33.36 V (8.34%)366.6 V55.03 V (13.76%)2600.1 WDrop High
2.5 mm²24 A18 A20.02 V (5.0%)380.0 V33.02 V (8.25%)1560.1 WDrop High
4 mm²32 A25 A12.51 V (3.13%)387.5 V20.64 V (5.16%)975.0 WDrop High
6 mm²41 A32 A8.34 V (2.08%)391.7 V13.76 V (3.44%)650.0 WDrop High
10 mm²57 A44 A5.0 V (1.25%)395.0 V8.25 V (2.06%)390.0 W✓ OK (≤3%)
16 mm²76 A59 A3.13 V (0.78%)396.9 V5.16 V (1.29%)243.8 W✓ OK (≤3%)
25 mm²101 A78 A2.0 V (0.5%)398.0 V3.3 V (0.83%)156.0 W✓ OK (≤3%)
35 mm²125 A97 A1.43 V (0.36%)398.6 V2.36 V (0.59%)111.4 W✓ OK (≤3%)
50 mm²151 A118 A1.0 V (0.25%)399.0 V1.65 V (0.41%)78.0 W✓ OK (≤3%)
70 mm²192 A150 A0.71 V (0.18%)399.3 V1.18 V (0.29%)55.7 W✓ OK (≤3%)
95 mm²232 A181 A0.53 V (0.13%)399.5 V0.87 V (0.22%)41.1 W✓ OK (≤3%)
120 mm²269 A210 A0.42 V (0.1%)399.6 V0.69 V (0.17%)32.5 W✓ OK (≤3%)
150 mm²309 A241 A0.33 V (0.08%)399.7 V0.55 V (0.14%)26.0 W✓ OK (≤3%)
185 mm²353 A275 A0.27 V (0.07%)399.7 V0.45 V (0.11%)21.1 W✓ OK (≤3%)
240 mm²415 A324 A0.21 V (0.05%)399.8 V0.34 V (0.09%)16.3 W✓ OK (≤3%)
300 mm²477 A372 A0.17 V (0.04%)399.8 V0.28 V (0.07%)13.0 W✓ OK (≤3%)
400 mm²570 A445 A0.13 V (0.03%)399.9 V0.21 V (0.05%)9.8 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 45 Ampere bei 30 Meter (400V)

Welcher Kabelquerschnitt wird für 45A bei 30m (400V) benötigt?

Für 45 Ampere über 30 Meter bei 400V wird ein Kupferkabel von 10 mm² empfohlen, um den Spannungsfall unter 3% (5.0V bzw. 1.25%) zu halten.

Wie hoch ist die maximale Leistung bei 45A und 400V?

Die übertragbare Leistung beträgt 31.18 kW bei einer empfohlenen Absicherung von 45A.