Kabelquerschnitt für 45 Ampere bei 350 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 45 A über 350 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)50 mm²Drop: 11.68V (2.92%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 10.14V (2.53%)
Voltage at Load388.3 VLine Loss: 910.0 W
Max Power & Breaker31.18 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A389.19 V (97.3%)10.8 V641.98 V (160.5%)30334.5 WDrop High
2.5 mm²24 A18 A233.52 V (58.38%)166.5 V385.19 V (96.3%)18200.7 WDrop High
4 mm²32 A25 A145.95 V (36.49%)254.1 V240.74 V (60.19%)11375.4 WDrop High
6 mm²41 A32 A97.3 V (24.32%)302.7 V160.5 V (40.12%)7583.6 WDrop High
10 mm²57 A44 A58.38 V (14.59%)341.6 V96.3 V (24.07%)4550.2 WDrop High
16 mm²76 A59 A36.49 V (9.12%)363.5 V60.19 V (15.05%)2843.9 WDrop High
25 mm²101 A78 A23.35 V (5.84%)376.6 V38.52 V (9.63%)1820.1 WDrop High
35 mm²125 A97 A16.68 V (4.17%)383.3 V27.51 V (6.88%)1300.0 W~ ≤5%
50 mm²151 A118 A11.68 V (2.92%)388.3 V19.26 V (4.81%)910.0 W✓ OK (≤3%)
70 mm²192 A150 A8.34 V (2.08%)391.7 V13.76 V (3.44%)650.0 W✓ OK (≤3%)
95 mm²232 A181 A6.15 V (1.54%)393.9 V10.14 V (2.53%)479.0 W✓ OK (≤3%)
120 mm²269 A210 A4.86 V (1.22%)395.1 V8.02 V (2.01%)379.2 W✓ OK (≤3%)
150 mm²309 A241 A3.89 V (0.97%)396.1 V6.42 V (1.6%)303.3 W✓ OK (≤3%)
185 mm²353 A275 A3.16 V (0.79%)396.8 V5.21 V (1.3%)246.0 W✓ OK (≤3%)
240 mm²415 A324 A2.43 V (0.61%)397.6 V4.01 V (1.0%)189.6 W✓ OK (≤3%)
300 mm²477 A372 A1.95 V (0.49%)398.1 V3.21 V (0.8%)151.7 W✓ OK (≤3%)
400 mm²570 A445 A1.46 V (0.36%)398.5 V2.41 V (0.6%)113.8 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 45 Ampere bei 350 Meter (400V)

Welcher Kabelquerschnitt wird für 45A bei 350m (400V) benötigt?

Für 45 Ampere über 350 Meter bei 400V wird ein Kupferkabel von 50 mm² empfohlen, um den Spannungsfall unter 3% (11.68V bzw. 2.92%) zu halten.

Wie hoch ist die maximale Leistung bei 45A und 400V?

Die übertragbare Leistung beträgt 31.18 kW bei einer empfohlenen Absicherung von 45A.