⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 550 Ampere bei 600 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 550 A über 600 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)3× 400 mm²Drop: 10.19V (2.55%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 50.44V (12.61%)
Voltage at Load389.8 VLine Loss: 9710.2 W
Max Power & Breaker381.05 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A8154.5 V (2038.62%)0.0 V13451.11 V (3362.78%)7768200.0 WDrop High
2.5 mm²24 A18 A4892.7 V (1223.17%)0.0 V8070.66 V (2017.67%)4660920.0 WDrop High
4 mm²32 A25 A3057.94 V (764.48%)0.0 V5044.16 V (1261.04%)2913075.0 WDrop High
6 mm²41 A32 A2038.62 V (509.66%)0.0 V3362.78 V (840.69%)1942050.0 WDrop High
10 mm²57 A44 A1223.17 V (305.79%)0.0 V2017.67 V (504.42%)1165230.0 WDrop High
16 mm²76 A59 A764.48 V (191.12%)0.0 V1261.04 V (315.26%)728268.8 WDrop High
25 mm²101 A78 A489.27 V (122.32%)0.0 V807.07 V (201.77%)466092.0 WDrop High
35 mm²125 A97 A349.48 V (87.37%)50.5 V576.48 V (144.12%)332922.9 WDrop High
50 mm²151 A118 A244.63 V (61.16%)155.4 V403.53 V (100.88%)233046.0 WDrop High
70 mm²192 A150 A174.74 V (43.68%)225.3 V288.24 V (72.06%)166461.4 WDrop High
95 mm²232 A181 A128.76 V (32.19%)271.2 V212.39 V (53.1%)122655.8 WDrop High
120 mm²269 A210 A101.93 V (25.48%)298.1 V168.14 V (42.03%)97102.5 WDrop High
150 mm²309 A241 A81.54 V (20.39%)318.5 V134.51 V (33.63%)77682.0 WDrop High
185 mm²353 A275 A66.12 V (16.53%)333.9 V109.06 V (27.27%)62985.4 WDrop High
240 mm²415 A324 A50.97 V (12.74%)349.0 V84.07 V (21.02%)48551.2 WDrop High
300 mm²477 A372 A40.77 V (10.19%)359.2 V67.26 V (16.81%)38841.0 WDrop High
400 mm²570 A445 A30.58 V (7.64%)369.4 V50.44 V (12.61%)29130.7 WDrop High

FAQ — Kabelquerschnitt für 550 Ampere bei 600 Meter (400V)

Welcher Kabelquerschnitt wird für 550A bei 600m (400V) benötigt?

Für 550 Ampere über 600 Meter bei 400V wird ein Kupferkabel von 3× 400 mm² empfohlen, um den Spannungsfall unter 3% (10.19V bzw. 2.55%) zu halten.

Wie hoch ist die maximale Leistung bei 550A und 400V?

Die übertragbare Leistung beträgt 381.05 kW bei einer empfohlenen Absicherung von 600A.