Kabelquerschnitt für 700 Ampere bei 500 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 700 A über 500 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)3× 400 mm²Drop: 10.81V (2.7%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 53.5V (13.37%)
Voltage at Load389.2 VLine Loss: 13107.5 W
Max Power & Breaker484.97 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A8648.71 V (2162.18%)0.0 V14266.33 V (3566.58%)10486000.0 WDrop High
2.5 mm²24 A18 A5189.22 V (1297.31%)0.0 V8559.8 V (2139.95%)6291600.0 WDrop High
4 mm²32 A25 A3243.27 V (810.82%)0.0 V5349.87 V (1337.47%)3932250.0 WDrop High
6 mm²41 A32 A2162.18 V (540.54%)0.0 V3566.58 V (891.65%)2621500.0 WDrop High
10 mm²57 A44 A1297.31 V (324.33%)0.0 V2139.95 V (534.99%)1572900.0 WDrop High
16 mm²76 A59 A810.82 V (202.7%)0.0 V1337.47 V (334.37%)983062.5 WDrop High
25 mm²101 A78 A518.92 V (129.73%)0.0 V855.98 V (213.99%)629160.0 WDrop High
35 mm²125 A97 A370.66 V (92.66%)29.3 V611.41 V (152.85%)449400.0 WDrop High
50 mm²151 A118 A259.46 V (64.87%)140.5 V427.99 V (107.0%)314580.0 WDrop High
70 mm²192 A150 A185.33 V (46.33%)214.7 V305.71 V (76.43%)224700.0 WDrop High
95 mm²232 A181 A136.56 V (34.14%)263.4 V225.26 V (56.31%)165568.4 WDrop High
120 mm²269 A210 A108.11 V (27.03%)291.9 V178.33 V (44.58%)131075.0 WDrop High
150 mm²309 A241 A86.49 V (21.62%)313.5 V142.66 V (35.67%)104860.0 WDrop High
185 mm²353 A275 A70.12 V (17.53%)329.9 V115.67 V (28.92%)85021.6 WDrop High
240 mm²415 A324 A54.05 V (13.51%)345.9 V89.16 V (22.29%)65537.5 WDrop High
300 mm²477 A372 A43.24 V (10.81%)356.8 V71.33 V (17.83%)52430.0 WDrop High
400 mm²570 A445 A32.43 V (8.11%)367.6 V53.5 V (13.37%)39322.5 WDrop High

FAQ — Kabelquerschnitt für 700 Ampere bei 500 Meter (400V)

Welcher Kabelquerschnitt wird für 700A bei 500m (400V) benötigt?

Für 700 Ampere über 500 Meter bei 400V wird ein Kupferkabel von 3× 400 mm² empfohlen, um den Spannungsfall unter 3% (10.81V bzw. 2.7%) zu halten.

Wie hoch ist die maximale Leistung bei 700A und 400V?

Die übertragbare Leistung beträgt 484.97 kW bei einer empfohlenen Absicherung von 700A.