⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 90 Ampere bei 120 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 90 A über 120 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 11.44V (2.86%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 9.43V (2.36%)
Voltage at Load388.6 VLine Loss: 1782.9 W
Max Power & Breaker62.35 kW90A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 90A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A266.87 V (66.72%)133.1 V440.22 V (110.05%)41601.6 WDrop High
2.5 mm²24 A18 A160.12 V (40.03%)239.9 V264.13 V (66.03%)24961.0 WDrop High
4 mm²32 A25 A100.08 V (25.02%)299.9 V165.08 V (41.27%)15600.6 WDrop High
6 mm²41 A32 A66.72 V (16.68%)333.3 V110.05 V (27.51%)10400.4 WDrop High
10 mm²57 A44 A40.03 V (10.01%)360.0 V66.03 V (16.51%)6240.2 WDrop High
16 mm²76 A59 A25.02 V (6.25%)375.0 V41.27 V (10.32%)3900.2 WDrop High
25 mm²101 A78 A16.01 V (4.0%)384.0 V26.41 V (6.6%)2496.1 W~ ≤5%
35 mm²125 A97 A11.44 V (2.86%)388.6 V18.87 V (4.72%)1782.9 W✓ OK (≤3%)
50 mm²151 A118 A8.01 V (2.0%)392.0 V13.21 V (3.3%)1248.0 W✓ OK (≤3%)
70 mm²192 A150 A5.72 V (1.43%)394.3 V9.43 V (2.36%)891.5 W✓ OK (≤3%)
95 mm²232 A181 A4.21 V (1.05%)395.8 V6.95 V (1.74%)656.9 W✓ OK (≤3%)
120 mm²269 A210 A3.34 V (0.83%)396.7 V5.5 V (1.38%)520.0 W✓ OK (≤3%)
150 mm²309 A241 A2.67 V (0.67%)397.3 V4.4 V (1.1%)416.0 W✓ OK (≤3%)
185 mm²353 A275 A2.16 V (0.54%)397.8 V3.57 V (0.89%)337.3 W✓ OK (≤3%)
240 mm²415 A324 A1.67 V (0.42%)398.3 V2.75 V (0.69%)260.0 W✓ OK (≤3%)
300 mm²477 A372 A1.33 V (0.33%)398.7 V2.2 V (0.55%)208.0 W✓ OK (≤3%)
400 mm²570 A445 A1.0 V (0.25%)399.0 V1.65 V (0.41%)156.0 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 90 Ampere bei 120 Meter (400V)

Welcher Kabelquerschnitt wird für 90A bei 120m (400V) benötigt?

Für 90 Ampere über 120 Meter bei 400V wird ein Kupferkabel von 35 mm² empfohlen, um den Spannungsfall unter 3% (11.44V bzw. 2.86%) zu halten.

Wie hoch ist die maximale Leistung bei 90A und 400V?

Die übertragbare Leistung beträgt 62.35 kW bei einer empfohlenen Absicherung von 90A.