1500 kVA to Amps at 480V Three-Phase AC (US Industrial)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 1500 kVA on a 480V Three-Phase AC (US Industrial) circuit.

Line Current (0.85 PF)1804.22 AAt 1.0 PF: 1804.22 A
Active / Apparent Power1275.0 kW1500.0 kVA · 790.17 kVAR
Recommended Breaker2500 A (NEC)2000 A (IEC Nominal)
Recommended Copper Wire4× 1000 kcmil (Parallel)IEC Metric: 4× 400 mm²

Engineering Breakdown for 1500 kVA at 480V

Input Rating1500 kVA (480V Three-Phase AC (US Industrial))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)1804.22 Amps
Amperage at 1.00 Power Factor (Resistive Load)1804.22 Amps
Real Power (kW / Watts)1275.0 kW (1,275,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)1500.0 kVA / 790.17 kVAR
Equivalent Mechanical Horsepower (HP)1709.8 HP
NEC 125% Continuous Circuit Breaker2500 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)4× 1000 kcmil (Parallel) (NEC) / 4× 400 mm² (IEC)

Frequently Asked Questions

How many amps is 1500 kVA at 480V (3-Phase)?

At 480V Three-Phase AC (US Industrial), 1500 kVA equals 1804.22 Amps at an industrial power factor of 0.85 (or 1804.22 Amps at unity power factor 1.0).

What size breaker and wire is needed for 1500 kVA at 480V?

For 1804.22A continuous load, NEC requires a 125% rated breaker of 2500A with 4× 1000 kcmil (Parallel) copper conductors, while IEC standard sizing uses a 2000A breaker with 4× 400 mm² copper cable.