⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🏭 Industrial Electrical Conversion · Three-Phase & Single-Phase

80 kVA to Amps at 480V Three-Phase AC (US Industrial)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 80 kVA on a 480V Three-Phase AC (US Industrial) circuit.

Line Current (0.85 PF)96.23 AAt 1.0 PF: 96.23 A
Active / Apparent Power68.0 kW80.0 kVA · 42.14 kVAR
Recommended Breaker125 A (NEC)100 A (IEC Nominal)
Recommended Copper Wire3 AWGIEC Metric: 25 mm²

Engineering Breakdown for 80 kVA at 480V

Input Rating80 kVA (480V Three-Phase AC (US Industrial))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)96.23 Amps
Amperage at 1.00 Power Factor (Resistive Load)96.23 Amps
Real Power (kW / Watts)68.0 kW (68,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)80.0 kVA / 42.14 kVAR
Equivalent Mechanical Horsepower (HP)91.19 HP
NEC 125% Continuous Circuit Breaker125 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)3 AWG (NEC) / 25 mm² (IEC)

Frequently Asked Questions

How many amps is 80 kVA at 480V (3-Phase)?

At 480V Three-Phase AC (US Industrial), 80 kVA equals 96.23 Amps at an industrial power factor of 0.85 (or 96.23 Amps at unity power factor 1.0).

What size breaker and wire is needed for 80 kVA at 480V?

For 96.23A continuous load, NEC requires a 125% rated breaker of 125A with 3 AWG copper conductors, while IEC standard sizing uses a 100A breaker with 25 mm² copper cable.