120 kW to Amps at 240V Single-Phase AC (NEC)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 120 kW on a 240V Single-Phase AC (NEC) circuit.

Line Current (0.85 PF)588.24 AAt 1.0 PF: 500.0 A
Active / Apparent Power120.0 kW141.18 kVA · 74.37 kVAR
Recommended Breaker800 A (NEC)600 A (IEC Nominal)
Recommended Copper Wire2× 1000 kcmil (Parallel)IEC Metric: 2× 400 mm²

Engineering Breakdown for 120 kW at 240V

Input Rating120 kW (240V Single-Phase AC (NEC))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)588.24 Amps
Amperage at 1.00 Power Factor (Resistive Load)500.0 Amps
Real Power (kW / Watts)120.0 kW (120,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)141.18 kVA / 74.37 kVAR
Equivalent Mechanical Horsepower (HP)160.92 HP
NEC 125% Continuous Circuit Breaker800 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)2× 1000 kcmil (Parallel) (NEC) / 2× 400 mm² (IEC)

Frequently Asked Questions

How many amps is 120 kW at 240V (1-Phase)?

At 240V Single-Phase AC (NEC), 120 kW equals 588.24 Amps at an industrial power factor of 0.85 (or 500.0 Amps at unity power factor 1.0).

What size breaker and wire is needed for 120 kW at 240V?

For 588.24A continuous load, NEC requires a 125% rated breaker of 800A with 2× 1000 kcmil (Parallel) copper conductors, while IEC standard sizing uses a 600A breaker with 2× 400 mm² copper cable.