170 kW to Amps at 415V Three-Phase AC (UK / AU)

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 170 kW on a 415V Three-Phase AC (UK / AU) circuit.

Line Current (0.85 PF)278.24 AAt 1.0 PF: 236.5 A
Active / Apparent Power170.0 kW200.0 kVA · 105.36 kVAR
Recommended Breaker350 A (NEC)300 A (IEC Nominal)
Recommended Copper Wire300 kcmilIEC Metric: 150 mm²

Engineering Breakdown for 170 kW at 415V

Input Rating170 kW (415V Three-Phase AC (UK / AU))
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)278.24 Amps
Amperage at 1.00 Power Factor (Resistive Load)236.5 Amps
Real Power (kW / Watts)170.0 kW (170,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)200.0 kVA / 105.36 kVAR
Equivalent Mechanical Horsepower (HP)227.97 HP
NEC 125% Continuous Circuit Breaker350 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)300 kcmil (NEC) / 150 mm² (IEC)

Frequently Asked Questions

How many amps is 170 kW at 415V (3-Phase)?

At 415V Three-Phase AC (UK / AU), 170 kW equals 278.24 Amps at an industrial power factor of 0.85 (or 236.5 Amps at unity power factor 1.0).

What size breaker and wire is needed for 170 kW at 415V?

For 278.24A continuous load, NEC requires a 125% rated breaker of 350A with 300 kcmil copper conductors, while IEC standard sizing uses a 300A breaker with 150 mm² copper cable.