170 kW to Amps at 480V Three-Phase AC (US Industrial)
Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 170 kW on a 480V Three-Phase AC (US Industrial) circuit.
Line Current (0.85 PF)240.56 AAt 1.0 PF: 204.48 A
Active / Apparent Power170.0 kW200.0 kVA · 105.36 kVAR
Recommended Breaker350 A (NEC)250 A (IEC Nominal)
Recommended Copper Wire250 kcmilIEC Metric: 120 mm²
Engineering Breakdown for 170 kW at 480V
| Input Rating | 170 kW (480V Three-Phase AC (US Industrial)) |
| Amperage at 0.85 Power Factor (Industrial Motor/Transformer) | 240.56 Amps |
| Amperage at 1.00 Power Factor (Resistive Load) | 204.48 Amps |
| Real Power (kW / Watts) | 170.0 kW (170,000 W) |
| Apparent Power (kVA) & Reactive Power (kVAR) | 200.0 kVA / 105.36 kVAR |
| Equivalent Mechanical Horsepower (HP) | 227.97 HP |
| NEC 125% Continuous Circuit Breaker | 350 A |
| Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop) | 250 kcmil (NEC) / 120 mm² (IEC) |
Frequently Asked Questions
How many amps is 170 kW at 480V (3-Phase)?
At 480V Three-Phase AC (US Industrial), 170 kW equals 240.56 Amps at an industrial power factor of 0.85 (or 204.48 Amps at unity power factor 1.0).
What size breaker and wire is needed for 170 kW at 480V?
For 240.56A continuous load, NEC requires a 125% rated breaker of 350A with 250 kcmil copper conductors, while IEC standard sizing uses a 250A breaker with 120 mm² copper cable.
Other Power Ratings & Voltages
5 kW at 480V (3P)10 kW at 480V (3P)15 kW at 480V (3P)20 kW at 480V (3P)25 kW at 480V (3P)30 kW at 480V (3P)45 kW at 480V (3P)50 kW at 480V (3P)75 kW at 480V (3P)100 kW at 480V (3P)150 kW at 480V (3P)200 kW at 480V (3P)250 kW at 480V (3P)500 kW at 480V (3P)170 kW at 120V Single-Phase AC170 kW at 208V Single-Phase AC170 kW at 230V Single-Phase AC (IEC)170 kW at 240V Single-Phase AC (NEC)170 kW at 208V Three-Phase AC170 kW at 230V Three-Phase AC170 kW at 400V Three-Phase AC (IEC Europe)170 kW at 415V Three-Phase AC (UK / AU)170 kW at 600V Three-Phase AC (Canada / Heavy)170 kW at 24V DC Direct Current170 kW at 48V DC Battery / Telecom Bus