5.5 kW to Amps at 230V Three-Phase AC

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 5.5 kW on a 230V Three-Phase AC circuit.

Line Current (0.85 PF)16.24 AAt 1.0 PF: 13.81 A
Active / Apparent Power5.5 kW6.47 kVA · 3.41 kVAR
Recommended Breaker25 A (NEC)20 A (IEC Nominal)
Recommended Copper Wire12 AWGIEC Metric: 2.5 mm²

Engineering Breakdown for 5.5 kW at 230V

Input Rating5.5 kW (230V Three-Phase AC)
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)16.24 Amps
Amperage at 1.00 Power Factor (Resistive Load)13.81 Amps
Real Power (kW / Watts)5.5 kW (5,500 W)
Apparent Power (kVA) & Reactive Power (kVAR)6.47 kVA / 3.41 kVAR
Equivalent Mechanical Horsepower (HP)7.38 HP
NEC 125% Continuous Circuit Breaker25 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)12 AWG (NEC) / 2.5 mm² (IEC)

Frequently Asked Questions

How many amps is 5.5 kW at 230V (3-Phase)?

At 230V Three-Phase AC, 5.5 kW equals 16.24 Amps at an industrial power factor of 0.85 (or 13.81 Amps at unity power factor 1.0).

What size breaker and wire is needed for 5.5 kW at 230V?

For 16.24A continuous load, NEC requires a 125% rated breaker of 25A with 12 AWG copper conductors, while IEC standard sizing uses a 20A breaker with 2.5 mm² copper cable.