8 kW to Amps at 208V Single-Phase AC

Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 8 kW on a 208V Single-Phase AC circuit.

Line Current (0.85 PF)45.25 AAt 1.0 PF: 38.46 A
Active / Apparent Power8.0 kW9.41 kVA · 4.96 kVAR
Recommended Breaker60 A (NEC)50 A (IEC Nominal)
Recommended Copper Wire8 AWGIEC Metric: 10 mm²

Engineering Breakdown for 8 kW at 208V

Input Rating8 kW (208V Single-Phase AC)
Amperage at 0.85 Power Factor (Industrial Motor/Transformer)45.25 Amps
Amperage at 1.00 Power Factor (Resistive Load)38.46 Amps
Real Power (kW / Watts)8.0 kW (8,000 W)
Apparent Power (kVA) & Reactive Power (kVAR)9.41 kVA / 4.96 kVAR
Equivalent Mechanical Horsepower (HP)10.73 HP
NEC 125% Continuous Circuit Breaker60 A
Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop)8 AWG (NEC) / 10 mm² (IEC)

Frequently Asked Questions

How many amps is 8 kW at 208V (1-Phase)?

At 208V Single-Phase AC, 8 kW equals 45.25 Amps at an industrial power factor of 0.85 (or 38.46 Amps at unity power factor 1.0).

What size breaker and wire is needed for 8 kW at 208V?

For 45.25A continuous load, NEC requires a 125% rated breaker of 60A with 8 AWG copper conductors, while IEC standard sizing uses a 50A breaker with 10 mm² copper cable.