8 kW to Amps at 208V Single-Phase AC
Exact current (Amps), real power (kW), apparent power (kVA), mechanical horsepower (HP), breaker rating, and conductor size for 8 kW on a 208V Single-Phase AC circuit.
Line Current (0.85 PF)45.25 AAt 1.0 PF: 38.46 A
Active / Apparent Power8.0 kW9.41 kVA · 4.96 kVAR
Recommended Breaker60 A (NEC)50 A (IEC Nominal)
Recommended Copper Wire8 AWGIEC Metric: 10 mm²
Engineering Breakdown for 8 kW at 208V
| Input Rating | 8 kW (208V Single-Phase AC) |
| Amperage at 0.85 Power Factor (Industrial Motor/Transformer) | 45.25 Amps |
| Amperage at 1.00 Power Factor (Resistive Load) | 38.46 Amps |
| Real Power (kW / Watts) | 8.0 kW (8,000 W) |
| Apparent Power (kVA) & Reactive Power (kVAR) | 9.41 kVA / 4.96 kVAR |
| Equivalent Mechanical Horsepower (HP) | 10.73 HP |
| NEC 125% Continuous Circuit Breaker | 60 A |
| Minimum Copper Conductor (100 ft / 30 m, ≤3% Drop) | 8 AWG (NEC) / 10 mm² (IEC) |
Frequently Asked Questions
How many amps is 8 kW at 208V (1-Phase)?
At 208V Single-Phase AC, 8 kW equals 45.25 Amps at an industrial power factor of 0.85 (or 38.46 Amps at unity power factor 1.0).
What size breaker and wire is needed for 8 kW at 208V?
For 45.25A continuous load, NEC requires a 125% rated breaker of 60A with 8 AWG copper conductors, while IEC standard sizing uses a 50A breaker with 10 mm² copper cable.
Other Power Ratings & Voltages
5 kW at 208V (1P)10 kW at 208V (1P)15 kW at 208V (1P)20 kW at 208V (1P)25 kW at 208V (1P)30 kW at 208V (1P)45 kW at 208V (1P)50 kW at 208V (1P)75 kW at 208V (1P)100 kW at 208V (1P)150 kW at 208V (1P)200 kW at 208V (1P)250 kW at 208V (1P)500 kW at 208V (1P)8 kW at 120V Single-Phase AC8 kW at 230V Single-Phase AC (IEC)8 kW at 240V Single-Phase AC (NEC)8 kW at 208V Three-Phase AC8 kW at 230V Three-Phase AC8 kW at 400V Three-Phase AC (IEC Europe)8 kW at 415V Three-Phase AC (UK / AU)8 kW at 480V Three-Phase AC (US Industrial)8 kW at 600V Three-Phase AC (Canada / Heavy)8 kW at 24V DC Direct Current8 kW at 48V DC Battery / Telecom Bus