Kabeltverrsnitt for 200 Ampere ved 80 Meter (400V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 200 A over 80 m ved 400V.

Copper Cable (≤3% Drop)95 mm²Drop: 6.24V (1.56%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 8.15V (2.04%)
Voltage at Load393.8 VLine Loss: 2162.5 W
Max Power & Breaker138.56 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A395.37 V (98.84%)4.6 V652.17 V (163.04%)136960.0 WDrop High
2.5 mm²24 A18 A237.22 V (59.31%)162.8 V391.3 V (97.83%)82176.0 WDrop High
4 mm²32 A25 A148.26 V (37.07%)251.7 V244.57 V (61.14%)51360.0 WDrop High
6 mm²41 A32 A98.84 V (24.71%)301.2 V163.04 V (40.76%)34240.0 WDrop High
10 mm²57 A44 A59.31 V (14.83%)340.7 V97.83 V (24.46%)20544.0 WDrop High
16 mm²76 A59 A37.07 V (9.27%)362.9 V61.14 V (15.29%)12840.0 WDrop High
25 mm²101 A78 A23.72 V (5.93%)376.3 V39.13 V (9.78%)8217.6 WDrop High
35 mm²125 A97 A16.94 V (4.24%)383.1 V27.95 V (6.99%)5869.7 WDrop High
50 mm²151 A118 A11.86 V (2.97%)388.1 V19.57 V (4.89%)4108.8 WDrop High
70 mm²192 A150 A8.47 V (2.12%)391.5 V13.98 V (3.49%)2934.9 WDrop High
95 mm²232 A181 A6.24 V (1.56%)393.8 V10.3 V (2.57%)2162.5 W✓ OK (≤3%)
120 mm²269 A210 A4.94 V (1.24%)395.1 V8.15 V (2.04%)1712.0 W✓ OK (≤3%)
150 mm²309 A241 A3.95 V (0.99%)396.0 V6.52 V (1.63%)1369.6 W✓ OK (≤3%)
185 mm²353 A275 A3.21 V (0.8%)396.8 V5.29 V (1.32%)1110.5 W✓ OK (≤3%)
240 mm²415 A324 A2.47 V (0.62%)397.5 V4.08 V (1.02%)856.0 W✓ OK (≤3%)
300 mm²477 A372 A1.98 V (0.49%)398.0 V3.26 V (0.82%)684.8 W✓ OK (≤3%)
400 mm²570 A445 A1.48 V (0.37%)398.5 V2.45 V (0.61%)513.6 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 200 Ampere ved 80 Meter (400V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 200A over 80 meter (400V)?

Etter NEK 400 anbefales 95 mm² kobberkabel for 200A ved 80 meter (400V), som gir et spenningsfall på 6.24V (1.56%).

Hvor mange kW tåler 200A ved 400V?

Kursen leverer opptil 138.56 kW med 200A vern.