Kabeltverrsnitt for 63 Ampere ved 80 Meter (400V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 63 A over 80 m ved 400V.

Copper Cable (≤3% Drop)16 mm²Drop: 11.68V (2.92%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 8.8V (2.2%)
Voltage at Load388.3 VLine Loss: 1274.0 W
Max Power & Breaker43.65 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A124.54 V (31.14%)275.5 V205.44 V (51.36%)13589.9 WDrop High
2.5 mm²24 A18 A74.72 V (18.68%)325.3 V123.26 V (30.82%)8153.9 WDrop High
4 mm²32 A25 A46.7 V (11.68%)353.3 V77.04 V (19.26%)5096.2 WDrop High
6 mm²41 A32 A31.14 V (7.78%)368.9 V51.36 V (12.84%)3397.5 WDrop High
10 mm²57 A44 A18.68 V (4.67%)381.3 V30.82 V (7.7%)2038.5 WDrop High
16 mm²76 A59 A11.68 V (2.92%)388.3 V19.26 V (4.81%)1274.0 W✓ OK (≤3%)
25 mm²101 A78 A7.47 V (1.87%)392.5 V12.33 V (3.08%)815.4 W✓ OK (≤3%)
35 mm²125 A97 A5.34 V (1.33%)394.7 V8.8 V (2.2%)582.4 W✓ OK (≤3%)
50 mm²151 A118 A3.74 V (0.93%)396.3 V6.16 V (1.54%)407.7 W✓ OK (≤3%)
70 mm²192 A150 A2.67 V (0.67%)397.3 V4.4 V (1.1%)291.2 W✓ OK (≤3%)
95 mm²232 A181 A1.97 V (0.49%)398.0 V3.24 V (0.81%)214.6 W✓ OK (≤3%)
120 mm²269 A210 A1.56 V (0.39%)398.4 V2.57 V (0.64%)169.9 W✓ OK (≤3%)
150 mm²309 A241 A1.25 V (0.31%)398.8 V2.05 V (0.51%)135.9 W✓ OK (≤3%)
185 mm²353 A275 A1.01 V (0.25%)399.0 V1.67 V (0.42%)110.2 W✓ OK (≤3%)
240 mm²415 A324 A0.78 V (0.19%)399.2 V1.28 V (0.32%)84.9 W✓ OK (≤3%)
300 mm²477 A372 A0.62 V (0.16%)399.4 V1.03 V (0.26%)67.9 W✓ OK (≤3%)
400 mm²570 A445 A0.47 V (0.12%)399.5 V0.77 V (0.19%)51.0 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 63 Ampere ved 80 Meter (400V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 63A over 80 meter (400V)?

Etter NEK 400 anbefales 16 mm² kobberkabel for 63A ved 80 meter (400V), som gir et spenningsfall på 11.68V (2.92%).

Hvor mange kW tåler 63A ved 400V?

Kursen leverer opptil 43.65 kW med 63A vern.