⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltverrsnitt for 80 Ampere ved 80 Meter (400V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 80 A over 80 m ved 400V.

Copper Cable (≤3% Drop)25 mm²Drop: 9.49V (2.37%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 11.18V (2.8%)
Voltage at Load390.5 VLine Loss: 1314.8 W
Max Power & Breaker55.43 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A158.15 V (39.54%)241.9 V260.87 V (65.22%)21913.6 WDrop High
2.5 mm²24 A18 A94.89 V (23.72%)305.1 V156.52 V (39.13%)13148.2 WDrop High
4 mm²32 A25 A59.31 V (14.83%)340.7 V97.83 V (24.46%)8217.6 WDrop High
6 mm²41 A32 A39.54 V (9.88%)360.5 V65.22 V (16.3%)5478.4 WDrop High
10 mm²57 A44 A23.72 V (5.93%)376.3 V39.13 V (9.78%)3287.0 WDrop High
16 mm²76 A59 A14.83 V (3.71%)385.2 V24.46 V (6.11%)2054.4 WDrop High
25 mm²101 A78 A9.49 V (2.37%)390.5 V15.65 V (3.91%)1314.8 W✓ OK (≤3%)
35 mm²125 A97 A6.78 V (1.69%)393.2 V11.18 V (2.8%)939.2 W✓ OK (≤3%)
50 mm²151 A118 A4.74 V (1.19%)395.3 V7.83 V (1.96%)657.4 W✓ OK (≤3%)
70 mm²192 A150 A3.39 V (0.85%)396.6 V5.59 V (1.4%)469.6 W✓ OK (≤3%)
95 mm²232 A181 A2.5 V (0.62%)397.5 V4.12 V (1.03%)346.0 W✓ OK (≤3%)
120 mm²269 A210 A1.98 V (0.49%)398.0 V3.26 V (0.82%)273.9 W✓ OK (≤3%)
150 mm²309 A241 A1.58 V (0.4%)398.4 V2.61 V (0.65%)219.1 W✓ OK (≤3%)
185 mm²353 A275 A1.28 V (0.32%)398.7 V2.12 V (0.53%)177.7 W✓ OK (≤3%)
240 mm²415 A324 A0.99 V (0.25%)399.0 V1.63 V (0.41%)137.0 W✓ OK (≤3%)
300 mm²477 A372 A0.79 V (0.2%)399.2 V1.3 V (0.33%)109.6 W✓ OK (≤3%)
400 mm²570 A445 A0.59 V (0.15%)399.4 V0.98 V (0.24%)82.2 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 80 Ampere ved 80 Meter (400V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 80A over 80 meter (400V)?

Etter NEK 400 anbefales 25 mm² kobberkabel for 80A ved 80 meter (400V), som gir et spenningsfall på 9.49V (2.37%).

Hvor mange kW tåler 80A ved 400V?

Kursen leverer opptil 55.43 kW med 80A vern.