Kabeltverrsnitt for 225 Ampere ved 35 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 225 A over 35 m ved 230V.

Copper Cable (≤3% Drop)95 mm²Drop: 3.55V (1.54%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 3.71V (1.61%)
Voltage at Load226.5 VLine Loss: 798.3 W
Max Power & Breaker51.75 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A224.7 V (97.7%)5.3 V370.65 V (161.15%)50557.5 WDrop High
2.5 mm²24 A18 A134.82 V (58.62%)95.2 V222.39 V (96.69%)30334.5 WDrop High
4 mm²32 A25 A84.26 V (36.64%)145.7 V138.99 V (60.43%)18959.1 WDrop High
6 mm²41 A32 A56.18 V (24.42%)173.8 V92.66 V (40.29%)12639.4 WDrop High
10 mm²57 A44 A33.7 V (14.65%)196.3 V55.6 V (24.17%)7583.6 WDrop High
16 mm²76 A59 A21.07 V (9.16%)208.9 V34.75 V (15.11%)4739.8 WDrop High
25 mm²101 A78 A13.48 V (5.86%)216.5 V22.24 V (9.67%)3033.5 WDrop High
35 mm²125 A97 A9.63 V (4.19%)220.4 V15.88 V (6.91%)2166.8 WDrop High
50 mm²151 A118 A6.74 V (2.93%)223.3 V11.12 V (4.83%)1516.7 WDrop High
70 mm²192 A150 A4.81 V (2.09%)225.2 V7.94 V (3.45%)1083.4 WDrop High
95 mm²232 A181 A3.55 V (1.54%)226.5 V5.85 V (2.54%)798.3 W✓ OK (≤3%)
120 mm²269 A210 A2.81 V (1.22%)227.2 V4.63 V (2.01%)632.0 W✓ OK (≤3%)
150 mm²309 A241 A2.25 V (0.98%)227.8 V3.71 V (1.61%)505.6 W✓ OK (≤3%)
185 mm²353 A275 A1.82 V (0.79%)228.2 V3.01 V (1.31%)409.9 W✓ OK (≤3%)
240 mm²415 A324 A1.4 V (0.61%)228.6 V2.32 V (1.01%)316.0 W✓ OK (≤3%)
300 mm²477 A372 A1.12 V (0.49%)228.9 V1.85 V (0.81%)252.8 W✓ OK (≤3%)
400 mm²570 A445 A0.84 V (0.37%)229.2 V1.39 V (0.6%)189.6 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 225 Ampere ved 35 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 225A over 35 meter (230V)?

Etter NEK 400 anbefales 95 mm² kobberkabel for 225A ved 35 meter (230V), som gir et spenningsfall på 3.55V (1.54%).

Hvor mange kW tåler 225A ved 230V?

Kursen leverer opptil 51.75 kW med 225A vern.