Kabeltverrsnitt for 225 Ampere ved 5 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 225 A over 5 m ved 230V.

Copper Cable (≤3% Drop)95 mm²Drop: 0.51V (0.22%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 0.53V (0.23%)
Voltage at Load229.5 VLine Loss: 114.0 W
Max Power & Breaker51.75 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A32.1 V (13.96%)197.9 V52.95 V (23.02%)7222.5 WDrop High
2.5 mm²24 A18 A19.26 V (8.37%)210.7 V31.77 V (13.81%)4333.5 WDrop High
4 mm²32 A25 A12.04 V (5.23%)218.0 V19.86 V (8.63%)2708.4 WDrop High
6 mm²41 A32 A8.03 V (3.49%)222.0 V13.24 V (5.76%)1805.6 WDrop High
10 mm²57 A44 A4.81 V (2.09%)225.2 V7.94 V (3.45%)1083.4 WDrop High
16 mm²76 A59 A3.01 V (1.31%)227.0 V4.96 V (2.16%)677.1 WDrop High
25 mm²101 A78 A1.93 V (0.84%)228.1 V3.18 V (1.38%)433.4 WDrop High
35 mm²125 A97 A1.38 V (0.6%)228.6 V2.27 V (0.99%)309.5 WDrop High
50 mm²151 A118 A0.96 V (0.42%)229.0 V1.59 V (0.69%)216.7 WDrop High
70 mm²192 A150 A0.69 V (0.3%)229.3 V1.13 V (0.49%)154.8 WDrop High
95 mm²232 A181 A0.51 V (0.22%)229.5 V0.84 V (0.36%)114.0 W✓ OK (≤3%)
120 mm²269 A210 A0.4 V (0.17%)229.6 V0.66 V (0.29%)90.3 W✓ OK (≤3%)
150 mm²309 A241 A0.32 V (0.14%)229.7 V0.53 V (0.23%)72.2 W✓ OK (≤3%)
185 mm²353 A275 A0.26 V (0.11%)229.7 V0.43 V (0.19%)58.6 W✓ OK (≤3%)
240 mm²415 A324 A0.2 V (0.09%)229.8 V0.33 V (0.14%)45.1 W✓ OK (≤3%)
300 mm²477 A372 A0.16 V (0.07%)229.8 V0.26 V (0.12%)36.1 W✓ OK (≤3%)
400 mm²570 A445 A0.12 V (0.05%)229.9 V0.2 V (0.09%)27.1 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 225 Ampere ved 5 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 225A over 5 meter (230V)?

Etter NEK 400 anbefales 95 mm² kobberkabel for 225A ved 5 meter (230V), som gir et spenningsfall på 0.51V (0.22%).

Hvor mange kW tåler 225A ved 230V?

Kursen leverer opptil 51.75 kW med 225A vern.