⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltverrsnitt for 32 Ampere ved 35 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 32 A over 35 m ved 230V.

Copper Cable (≤3% Drop)10 mm²Drop: 4.79V (2.08%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 4.94V (2.15%)
Voltage at Load225.2 VLine Loss: 153.4 W
Max Power & Breaker7.36 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A31.96 V (13.89%)198.0 V52.71 V (22.92%)1022.6 WDrop High
2.5 mm²24 A18 A19.17 V (8.34%)210.8 V31.63 V (13.75%)613.6 WDrop High
4 mm²32 A25 A11.98 V (5.21%)218.0 V19.77 V (8.59%)383.5 WDrop High
6 mm²41 A32 A7.99 V (3.47%)222.0 V13.18 V (5.73%)255.7 W~ ≤5%
10 mm²57 A44 A4.79 V (2.08%)225.2 V7.91 V (3.44%)153.4 W✓ OK (≤3%)
16 mm²76 A59 A3.0 V (1.3%)227.0 V4.94 V (2.15%)95.9 W✓ OK (≤3%)
25 mm²101 A78 A1.92 V (0.83%)228.1 V3.16 V (1.38%)61.4 W✓ OK (≤3%)
35 mm²125 A97 A1.37 V (0.6%)228.6 V2.26 V (0.98%)43.8 W✓ OK (≤3%)
50 mm²151 A118 A0.96 V (0.42%)229.0 V1.58 V (0.69%)30.7 W✓ OK (≤3%)
70 mm²192 A150 A0.68 V (0.3%)229.3 V1.13 V (0.49%)21.9 W✓ OK (≤3%)
95 mm²232 A181 A0.5 V (0.22%)229.5 V0.83 V (0.36%)16.1 W✓ OK (≤3%)
120 mm²269 A210 A0.4 V (0.17%)229.6 V0.66 V (0.29%)12.8 W✓ OK (≤3%)
150 mm²309 A241 A0.32 V (0.14%)229.7 V0.53 V (0.23%)10.2 W✓ OK (≤3%)
185 mm²353 A275 A0.26 V (0.11%)229.7 V0.43 V (0.19%)8.3 W✓ OK (≤3%)
240 mm²415 A324 A0.2 V (0.09%)229.8 V0.33 V (0.14%)6.4 W✓ OK (≤3%)
300 mm²477 A372 A0.16 V (0.07%)229.8 V0.26 V (0.11%)5.1 W✓ OK (≤3%)
400 mm²570 A445 A0.12 V (0.05%)229.9 V0.2 V (0.09%)3.8 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 32 Ampere ved 35 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 32A over 35 meter (230V)?

Etter NEK 400 anbefales 10 mm² kobberkabel for 32A ved 35 meter (230V), som gir et spenningsfall på 4.79V (2.08%).

Hvor mange kW tåler 32A ved 230V?

Kursen leverer opptil 7.36 kW med 32A vern.