Kabeltverrsnitt for 30 Ampere ved 30 Meter (400V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 30 A over 30 m ved 400V.

Copper Cable (≤3% Drop)4 mm²Drop: 8.34V (2.08%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 9.17V (2.29%)
Voltage at Load391.7 VLine Loss: 433.4 W
Max Power & Breaker20.78 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A22.24 V (5.56%)377.8 V36.68 V (9.17%)1155.6 WDrop High
2.5 mm²24 A18 A13.34 V (3.34%)386.7 V22.01 V (5.5%)693.4 WDrop High
4 mm²32 A25 A8.34 V (2.08%)391.7 V13.76 V (3.44%)433.4 W✓ OK (≤3%)
6 mm²41 A32 A5.56 V (1.39%)394.4 V9.17 V (2.29%)288.9 W✓ OK (≤3%)
10 mm²57 A44 A3.34 V (0.83%)396.7 V5.5 V (1.38%)173.3 W✓ OK (≤3%)
16 mm²76 A59 A2.08 V (0.52%)397.9 V3.44 V (0.86%)108.3 W✓ OK (≤3%)
25 mm²101 A78 A1.33 V (0.33%)398.7 V2.2 V (0.55%)69.3 W✓ OK (≤3%)
35 mm²125 A97 A0.95 V (0.24%)399.0 V1.57 V (0.39%)49.5 W✓ OK (≤3%)
50 mm²151 A118 A0.67 V (0.17%)399.3 V1.1 V (0.28%)34.7 W✓ OK (≤3%)
70 mm²192 A150 A0.48 V (0.12%)399.5 V0.79 V (0.2%)24.8 W✓ OK (≤3%)
95 mm²232 A181 A0.35 V (0.09%)399.6 V0.58 V (0.14%)18.2 W✓ OK (≤3%)
120 mm²269 A210 A0.28 V (0.07%)399.7 V0.46 V (0.11%)14.4 W✓ OK (≤3%)
150 mm²309 A241 A0.22 V (0.06%)399.8 V0.37 V (0.09%)11.6 W✓ OK (≤3%)
185 mm²353 A275 A0.18 V (0.05%)399.8 V0.3 V (0.07%)9.4 W✓ OK (≤3%)
240 mm²415 A324 A0.14 V (0.03%)399.9 V0.23 V (0.06%)7.2 W✓ OK (≤3%)
300 mm²477 A372 A0.11 V (0.03%)399.9 V0.18 V (0.05%)5.8 W✓ OK (≤3%)
400 mm²570 A445 A0.08 V (0.02%)399.9 V0.14 V (0.03%)4.3 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 30 Ampere ved 30 Meter (400V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 30A over 30 meter (400V)?

Etter NEK 400 anbefales 4 mm² kobberkabel for 30A ved 30 meter (400V), som gir et spenningsfall på 8.34V (2.08%).

Hvor mange kW tåler 30A ved 400V?

Kursen leverer opptil 20.78 kW med 30A vern.