⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltverrsnitt for 30 Ampere ved 5 Meter (400V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 30 A over 5 m ved 400V.

Copper Cable (≤3% Drop)4 mm²Drop: 1.39V (0.35%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 1.53V (0.38%)
Voltage at Load398.6 VLine Loss: 72.2 W
Max Power & Breaker20.78 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3.71 V (0.93%)396.3 V6.11 V (1.53%)192.6 WDrop High
2.5 mm²24 A18 A2.22 V (0.56%)397.8 V3.67 V (0.92%)115.6 WDrop High
4 mm²32 A25 A1.39 V (0.35%)398.6 V2.29 V (0.57%)72.2 W✓ OK (≤3%)
6 mm²41 A32 A0.93 V (0.23%)399.1 V1.53 V (0.38%)48.1 W✓ OK (≤3%)
10 mm²57 A44 A0.56 V (0.14%)399.4 V0.92 V (0.23%)28.9 W✓ OK (≤3%)
16 mm²76 A59 A0.35 V (0.09%)399.7 V0.57 V (0.14%)18.1 W✓ OK (≤3%)
25 mm²101 A78 A0.22 V (0.06%)399.8 V0.37 V (0.09%)11.6 W✓ OK (≤3%)
35 mm²125 A97 A0.16 V (0.04%)399.8 V0.26 V (0.07%)8.3 W✓ OK (≤3%)
50 mm²151 A118 A0.11 V (0.03%)399.9 V0.18 V (0.05%)5.8 W✓ OK (≤3%)
70 mm²192 A150 A0.08 V (0.02%)399.9 V0.13 V (0.03%)4.1 W✓ OK (≤3%)
95 mm²232 A181 A0.06 V (0.01%)399.9 V0.1 V (0.02%)3.0 W✓ OK (≤3%)
120 mm²269 A210 A0.05 V (0.01%)400.0 V0.08 V (0.02%)2.4 W✓ OK (≤3%)
150 mm²309 A241 A0.04 V (0.01%)400.0 V0.06 V (0.02%)1.9 W✓ OK (≤3%)
185 mm²353 A275 A0.03 V (0.01%)400.0 V0.05 V (0.01%)1.6 W✓ OK (≤3%)
240 mm²415 A324 A0.02 V (0.01%)400.0 V0.04 V (0.01%)1.2 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.0%)400.0 V0.03 V (0.01%)1.0 W✓ OK (≤3%)
400 mm²570 A445 A0.01 V (0.0%)400.0 V0.02 V (0.01%)0.7 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 30 Ampere ved 5 Meter (400V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 30A over 5 meter (400V)?

Etter NEK 400 anbefales 4 mm² kobberkabel for 30A ved 5 meter (400V), som gir et spenningsfall på 1.39V (0.35%).

Hvor mange kW tåler 30A ved 400V?

Kursen leverer opptil 20.78 kW med 30A vern.