Kabeltverrsnitt for 32 Ampere ved 25 Meter (400V — NEK 400)
Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 32 A over 25 m ved 400V.
Copper Cable (≤3% Drop)4 mm²Drop: 7.41V (1.85%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 8.15V (2.04%)
Voltage at Load392.6 VLine Loss: 410.9 W
Max Power & Breaker22.17 kW32A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 25m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 19.77 V (4.94%) | 380.2 V | 32.61 V (8.15%) | 1095.7 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 11.86 V (2.97%) | 388.1 V | 19.57 V (4.89%) | 657.4 W | Drop High |
| 4 mm² | 32 A | 25 A | 7.41 V (1.85%) | 392.6 V | 12.23 V (3.06%) | 410.9 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 4.94 V (1.24%) | 395.1 V | 8.15 V (2.04%) | 273.9 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 2.97 V (0.74%) | 397.0 V | 4.89 V (1.22%) | 164.4 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 1.85 V (0.46%) | 398.1 V | 3.06 V (0.76%) | 102.7 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 1.19 V (0.3%) | 398.8 V | 1.96 V (0.49%) | 65.7 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.85 V (0.21%) | 399.2 V | 1.4 V (0.35%) | 47.0 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.59 V (0.15%) | 399.4 V | 0.98 V (0.24%) | 32.9 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.42 V (0.11%) | 399.6 V | 0.7 V (0.17%) | 23.5 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.31 V (0.08%) | 399.7 V | 0.51 V (0.13%) | 17.3 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.25 V (0.06%) | 399.8 V | 0.41 V (0.1%) | 13.7 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.2 V (0.05%) | 399.8 V | 0.33 V (0.08%) | 11.0 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.16 V (0.04%) | 399.8 V | 0.26 V (0.07%) | 8.9 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.12 V (0.03%) | 399.9 V | 0.2 V (0.05%) | 6.8 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.1 V (0.02%) | 399.9 V | 0.16 V (0.04%) | 5.5 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.07 V (0.02%) | 399.9 V | 0.12 V (0.03%) | 4.1 W | ✓ OK (≤3%) |
FAQ — Kabeltverrsnitt for 32 Ampere ved 25 Meter (400V — NEK 400)
Hvilket kabeltverrsnitt må jeg bruke for 32A over 25 meter (400V)?
Etter NEK 400 anbefales 4 mm² kobberkabel for 32A ved 25 meter (400V), som gir et spenningsfall på 7.41V (1.85%).
Hvor mange kW tåler 32A ved 400V?
Kursen leverer opptil 22.17 kW med 32A vern.
Related Lengths & Currents (400V)
32A · 5m (400V)32A · 10m (400V)32A · 15m (400V)32A · 20m (400V)32A · 30m (400V)32A · 35m (400V)32A · 40m (400V)32A · 45m (400V)32A · 50m (400V)32A · 60m (400V)32A · 70m (400V)10A · 25m (400V)16A · 25m (400V)20A · 25m (400V)25A · 25m (400V)40A · 25m (400V)50A · 25m (400V)63A · 25m (400V)80A · 25m (400V)100A · 25m (400V)125A · 25m (400V)160A · 25m (400V)200A · 25m (400V)