Kabeltverrsnitt for 32 Ampere ved 70 Meter (400V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 32 A over 70 m ved 400V.

Copper Cable (≤3% Drop)10 mm²Drop: 8.3V (2.08%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 8.56V (2.14%)
Voltage at Load391.7 VLine Loss: 460.2 W
Max Power & Breaker22.17 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A55.35 V (13.84%)344.6 V91.3 V (22.83%)3067.9 WDrop High
2.5 mm²24 A18 A33.21 V (8.3%)366.8 V54.78 V (13.7%)1840.7 WDrop High
4 mm²32 A25 A20.76 V (5.19%)379.2 V34.24 V (8.56%)1150.5 WDrop High
6 mm²41 A32 A13.84 V (3.46%)386.2 V22.83 V (5.71%)767.0 W~ ≤5%
10 mm²57 A44 A8.3 V (2.08%)391.7 V13.7 V (3.42%)460.2 W✓ OK (≤3%)
16 mm²76 A59 A5.19 V (1.3%)394.8 V8.56 V (2.14%)287.6 W✓ OK (≤3%)
25 mm²101 A78 A3.32 V (0.83%)396.7 V5.48 V (1.37%)184.1 W✓ OK (≤3%)
35 mm²125 A97 A2.37 V (0.59%)397.6 V3.91 V (0.98%)131.5 W✓ OK (≤3%)
50 mm²151 A118 A1.66 V (0.42%)398.3 V2.74 V (0.68%)92.0 W✓ OK (≤3%)
70 mm²192 A150 A1.19 V (0.3%)398.8 V1.96 V (0.49%)65.7 W✓ OK (≤3%)
95 mm²232 A181 A0.87 V (0.22%)399.1 V1.44 V (0.36%)48.4 W✓ OK (≤3%)
120 mm²269 A210 A0.69 V (0.17%)399.3 V1.14 V (0.29%)38.3 W✓ OK (≤3%)
150 mm²309 A241 A0.55 V (0.14%)399.4 V0.91 V (0.23%)30.7 W✓ OK (≤3%)
185 mm²353 A275 A0.45 V (0.11%)399.6 V0.74 V (0.19%)24.9 W✓ OK (≤3%)
240 mm²415 A324 A0.35 V (0.09%)399.7 V0.57 V (0.14%)19.2 W✓ OK (≤3%)
300 mm²477 A372 A0.28 V (0.07%)399.7 V0.46 V (0.11%)15.3 W✓ OK (≤3%)
400 mm²570 A445 A0.21 V (0.05%)399.8 V0.34 V (0.09%)11.5 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 32 Ampere ved 70 Meter (400V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 32A over 70 meter (400V)?

Etter NEK 400 anbefales 10 mm² kobberkabel for 32A ved 70 meter (400V), som gir et spenningsfall på 8.3V (2.08%).

Hvor mange kW tåler 32A ved 400V?

Kursen leverer opptil 22.17 kW med 32A vern.