⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltverrsnitt for 32 Ampere ved 60 Meter (400V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 32 A over 60 m ved 400V.

Copper Cable (≤3% Drop)6 mm²Drop: 11.86V (2.97%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 11.74V (2.93%)
Voltage at Load388.1 VLine Loss: 657.4 W
Max Power & Breaker22.17 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A47.44 V (11.86%)352.6 V78.26 V (19.57%)2629.6 WDrop High
2.5 mm²24 A18 A28.47 V (7.12%)371.5 V46.96 V (11.74%)1577.8 WDrop High
4 mm²32 A25 A17.79 V (4.45%)382.2 V29.35 V (7.34%)986.1 W~ ≤5%
6 mm²41 A32 A11.86 V (2.97%)388.1 V19.57 V (4.89%)657.4 W✓ OK (≤3%)
10 mm²57 A44 A7.12 V (1.78%)392.9 V11.74 V (2.93%)394.4 W✓ OK (≤3%)
16 mm²76 A59 A4.45 V (1.11%)395.6 V7.34 V (1.83%)246.5 W✓ OK (≤3%)
25 mm²101 A78 A2.85 V (0.71%)397.2 V4.7 V (1.17%)157.8 W✓ OK (≤3%)
35 mm²125 A97 A2.03 V (0.51%)398.0 V3.35 V (0.84%)112.7 W✓ OK (≤3%)
50 mm²151 A118 A1.42 V (0.36%)398.6 V2.35 V (0.59%)78.9 W✓ OK (≤3%)
70 mm²192 A150 A1.02 V (0.25%)399.0 V1.68 V (0.42%)56.3 W✓ OK (≤3%)
95 mm²232 A181 A0.75 V (0.19%)399.3 V1.24 V (0.31%)41.5 W✓ OK (≤3%)
120 mm²269 A210 A0.59 V (0.15%)399.4 V0.98 V (0.24%)32.9 W✓ OK (≤3%)
150 mm²309 A241 A0.47 V (0.12%)399.5 V0.78 V (0.2%)26.3 W✓ OK (≤3%)
185 mm²353 A275 A0.38 V (0.1%)399.6 V0.63 V (0.16%)21.3 W✓ OK (≤3%)
240 mm²415 A324 A0.3 V (0.07%)399.7 V0.49 V (0.12%)16.4 W✓ OK (≤3%)
300 mm²477 A372 A0.24 V (0.06%)399.8 V0.39 V (0.1%)13.1 W✓ OK (≤3%)
400 mm²570 A445 A0.18 V (0.04%)399.8 V0.29 V (0.07%)9.9 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 32 Ampere ved 60 Meter (400V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 32A over 60 meter (400V)?

Etter NEK 400 anbefales 6 mm² kobberkabel for 32A ved 60 meter (400V), som gir et spenningsfall på 11.86V (2.97%).

Hvor mange kW tåler 32A ved 400V?

Kursen leverer opptil 22.17 kW med 32A vern.