⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltverrsnitt for 32 Ampere ved 40 Meter (230V — NEK 400)

Nøyaktig beregning av kabeltverrsnitt (mm²), spenningsfall og sikring etter norsk standard NEK 400 for 32 A over 40 m ved 230V.

Copper Cable (≤3% Drop)10 mm²Drop: 5.48V (2.38%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 5.65V (2.46%)
Voltage at Load224.5 VLine Loss: 175.3 W
Max Power & Breaker7.36 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A36.52 V (15.88%)193.5 V60.25 V (26.19%)1168.7 WDrop High
2.5 mm²24 A18 A21.91 V (9.53%)208.1 V36.15 V (15.72%)701.2 WDrop High
4 mm²32 A25 A13.7 V (5.95%)216.3 V22.59 V (9.82%)438.3 WDrop High
6 mm²41 A32 A9.13 V (3.97%)220.9 V15.06 V (6.55%)292.2 W~ ≤5%
10 mm²57 A44 A5.48 V (2.38%)224.5 V9.04 V (3.93%)175.3 W✓ OK (≤3%)
16 mm²76 A59 A3.42 V (1.49%)226.6 V5.65 V (2.46%)109.6 W✓ OK (≤3%)
25 mm²101 A78 A2.19 V (0.95%)227.8 V3.61 V (1.57%)70.1 W✓ OK (≤3%)
35 mm²125 A97 A1.57 V (0.68%)228.4 V2.58 V (1.12%)50.1 W✓ OK (≤3%)
50 mm²151 A118 A1.1 V (0.48%)228.9 V1.81 V (0.79%)35.1 W✓ OK (≤3%)
70 mm²192 A150 A0.78 V (0.34%)229.2 V1.29 V (0.56%)25.0 W✓ OK (≤3%)
95 mm²232 A181 A0.58 V (0.25%)229.4 V0.95 V (0.41%)18.5 W✓ OK (≤3%)
120 mm²269 A210 A0.46 V (0.2%)229.5 V0.75 V (0.33%)14.6 W✓ OK (≤3%)
150 mm²309 A241 A0.37 V (0.16%)229.6 V0.6 V (0.26%)11.7 W✓ OK (≤3%)
185 mm²353 A275 A0.3 V (0.13%)229.7 V0.49 V (0.21%)9.5 W✓ OK (≤3%)
240 mm²415 A324 A0.23 V (0.1%)229.8 V0.38 V (0.16%)7.3 W✓ OK (≤3%)
300 mm²477 A372 A0.18 V (0.08%)229.8 V0.3 V (0.13%)5.8 W✓ OK (≤3%)
400 mm²570 A445 A0.14 V (0.06%)229.9 V0.23 V (0.1%)4.4 W✓ OK (≤3%)

FAQ — Kabeltverrsnitt for 32 Ampere ved 40 Meter (230V — NEK 400)

Hvilket kabeltverrsnitt må jeg bruke for 32A over 40 meter (230V)?

Etter NEK 400 anbefales 10 mm² kobberkabel for 32A ved 40 meter (230V), som gir et spenningsfall på 5.48V (2.38%).

Hvor mange kW tåler 32A ved 230V?

Kursen leverer opptil 7.36 kW med 32A vern.