Kabelarea för 10 Ampere vid 20 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 10 A över 20 m vid 230V.

Copper Cable (≤3% Drop)1.5 mm²Drop: 5.71V (2.48%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 5.65V (2.46%)
Voltage at Load224.3 VLine Loss: 57.1 W
Max Power & Breaker2.3 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5.71 V (2.48%)224.3 V9.41 V (4.09%)57.1 W✓ OK (≤3%)
2.5 mm²24 A18 A3.42 V (1.49%)226.6 V5.65 V (2.46%)34.2 W✓ OK (≤3%)
4 mm²32 A25 A2.14 V (0.93%)227.9 V3.53 V (1.53%)21.4 W✓ OK (≤3%)
6 mm²41 A32 A1.43 V (0.62%)228.6 V2.35 V (1.02%)14.3 W✓ OK (≤3%)
10 mm²57 A44 A0.86 V (0.37%)229.1 V1.41 V (0.61%)8.6 W✓ OK (≤3%)
16 mm²76 A59 A0.54 V (0.23%)229.5 V0.88 V (0.38%)5.3 W✓ OK (≤3%)
25 mm²101 A78 A0.34 V (0.15%)229.7 V0.56 V (0.25%)3.4 W✓ OK (≤3%)
35 mm²125 A97 A0.24 V (0.11%)229.8 V0.4 V (0.18%)2.4 W✓ OK (≤3%)
50 mm²151 A118 A0.17 V (0.07%)229.8 V0.28 V (0.12%)1.7 W✓ OK (≤3%)
70 mm²192 A150 A0.12 V (0.05%)229.9 V0.2 V (0.09%)1.2 W✓ OK (≤3%)
95 mm²232 A181 A0.09 V (0.04%)229.9 V0.15 V (0.06%)0.9 W✓ OK (≤3%)
120 mm²269 A210 A0.07 V (0.03%)229.9 V0.12 V (0.05%)0.7 W✓ OK (≤3%)
150 mm²309 A241 A0.06 V (0.02%)229.9 V0.09 V (0.04%)0.6 W✓ OK (≤3%)
185 mm²353 A275 A0.05 V (0.02%)230.0 V0.08 V (0.03%)0.5 W✓ OK (≤3%)
240 mm²415 A324 A0.04 V (0.02%)230.0 V0.06 V (0.03%)0.4 W✓ OK (≤3%)
300 mm²477 A372 A0.03 V (0.01%)230.0 V0.05 V (0.02%)0.3 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.01%)230.0 V0.04 V (0.02%)0.2 W✓ OK (≤3%)

FAQ — Kabelarea för 10 Ampere vid 20 Meter (230V)

Vilken kabelarea krävs för 10A vid 20 meter (230V)?

För 10 Ampere över 20 meter vid 230V rekommenderas 1.5 mm² kopparkabel för att hålla spänningsfallet under 3% (5.71V / 2.48%).

Hur stor effekt motsvarar 10A vid 230V?

Det motsvarar 2.3 kW med en rekommenderad säkring på 10A.