Kabelarea för 160 Ampere vid 20 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 160 A över 20 m vid 230V.
Copper Cable (≤3% Drop)70 mm²Drop: 1.96V (0.85%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 2.38V (1.03%)
Voltage at Load228.0 VLine Loss: 313.1 W
Max Power & Breaker36.8 kW160A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 20m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 91.31 V (39.7%) | 138.7 V | 150.61 V (65.48%) | 14609.1 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 54.78 V (23.82%) | 175.2 V | 90.37 V (39.29%) | 8765.4 W | Drop High |
| 4 mm² | 32 A | 25 A | 34.24 V (14.89%) | 195.8 V | 56.48 V (24.56%) | 5478.4 W | Drop High |
| 6 mm² | 41 A | 32 A | 22.83 V (9.92%) | 207.2 V | 37.65 V (16.37%) | 3652.3 W | Drop High |
| 10 mm² | 57 A | 44 A | 13.7 V (5.95%) | 216.3 V | 22.59 V (9.82%) | 2191.4 W | Drop High |
| 16 mm² | 76 A | 59 A | 8.56 V (3.72%) | 221.4 V | 14.12 V (6.14%) | 1369.6 W | Drop High |
| 25 mm² | 101 A | 78 A | 5.48 V (2.38%) | 224.5 V | 9.04 V (3.93%) | 876.5 W | Drop High |
| 35 mm² | 125 A | 97 A | 3.91 V (1.7%) | 226.1 V | 6.45 V (2.81%) | 626.1 W | Drop High |
| 50 mm² | 151 A | 118 A | 2.74 V (1.19%) | 227.3 V | 4.52 V (1.96%) | 438.3 W | Drop High |
| 70 mm² | 192 A | 150 A | 1.96 V (0.85%) | 228.0 V | 3.23 V (1.4%) | 313.1 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 1.44 V (0.63%) | 228.6 V | 2.38 V (1.03%) | 230.7 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 1.14 V (0.5%) | 228.9 V | 1.88 V (0.82%) | 182.6 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.91 V (0.4%) | 229.1 V | 1.51 V (0.65%) | 146.1 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.74 V (0.32%) | 229.3 V | 1.22 V (0.53%) | 118.5 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.57 V (0.25%) | 229.4 V | 0.94 V (0.41%) | 91.3 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.46 V (0.2%) | 229.5 V | 0.75 V (0.33%) | 73.0 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.34 V (0.15%) | 229.7 V | 0.56 V (0.25%) | 54.8 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 160 Ampere vid 20 Meter (230V)
Vilken kabelarea krävs för 160A vid 20 meter (230V)?
För 160 Ampere över 20 meter vid 230V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (1.96V / 0.85%).
Hur stor effekt motsvarar 160A vid 230V?
Det motsvarar 36.8 kW med en rekommenderad säkring på 160A.
Related Lengths & Currents (230V)
160A · 5m (230V)160A · 10m (230V)160A · 15m (230V)160A · 25m (230V)160A · 30m (230V)160A · 35m (230V)160A · 40m (230V)160A · 45m (230V)160A · 50m (230V)160A · 60m (230V)160A · 70m (230V)10A · 20m (230V)16A · 20m (230V)20A · 20m (230V)25A · 20m (230V)32A · 20m (230V)40A · 20m (230V)50A · 20m (230V)63A · 20m (230V)80A · 20m (230V)100A · 20m (230V)125A · 20m (230V)200A · 20m (230V)