Kabelarea för 10 Ampere vid 25 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 10 A över 25 m vid 230V.

Copper Cable (≤3% Drop)2.5 mm²Drop: 4.28V (1.86%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 4.41V (1.92%)
Voltage at Load225.7 VLine Loss: 42.8 W
Max Power & Breaker2.3 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7.13 V (3.1%)222.9 V11.77 V (5.12%)71.3 W~ ≤5%
2.5 mm²24 A18 A4.28 V (1.86%)225.7 V7.06 V (3.07%)42.8 W✓ OK (≤3%)
4 mm²32 A25 A2.67 V (1.16%)227.3 V4.41 V (1.92%)26.7 W✓ OK (≤3%)
6 mm²41 A32 A1.78 V (0.78%)228.2 V2.94 V (1.28%)17.8 W✓ OK (≤3%)
10 mm²57 A44 A1.07 V (0.47%)228.9 V1.76 V (0.77%)10.7 W✓ OK (≤3%)
16 mm²76 A59 A0.67 V (0.29%)229.3 V1.1 V (0.48%)6.7 W✓ OK (≤3%)
25 mm²101 A78 A0.43 V (0.19%)229.6 V0.71 V (0.31%)4.3 W✓ OK (≤3%)
35 mm²125 A97 A0.31 V (0.13%)229.7 V0.5 V (0.22%)3.1 W✓ OK (≤3%)
50 mm²151 A118 A0.21 V (0.09%)229.8 V0.35 V (0.15%)2.1 W✓ OK (≤3%)
70 mm²192 A150 A0.15 V (0.07%)229.8 V0.25 V (0.11%)1.5 W✓ OK (≤3%)
95 mm²232 A181 A0.11 V (0.05%)229.9 V0.19 V (0.08%)1.1 W✓ OK (≤3%)
120 mm²269 A210 A0.09 V (0.04%)229.9 V0.15 V (0.06%)0.9 W✓ OK (≤3%)
150 mm²309 A241 A0.07 V (0.03%)229.9 V0.12 V (0.05%)0.7 W✓ OK (≤3%)
185 mm²353 A275 A0.06 V (0.03%)229.9 V0.1 V (0.04%)0.6 W✓ OK (≤3%)
240 mm²415 A324 A0.04 V (0.02%)230.0 V0.07 V (0.03%)0.4 W✓ OK (≤3%)
300 mm²477 A372 A0.04 V (0.02%)230.0 V0.06 V (0.03%)0.4 W✓ OK (≤3%)
400 mm²570 A445 A0.03 V (0.01%)230.0 V0.04 V (0.02%)0.3 W✓ OK (≤3%)

FAQ — Kabelarea för 10 Ampere vid 25 Meter (230V)

Vilken kabelarea krävs för 10A vid 25 meter (230V)?

För 10 Ampere över 25 meter vid 230V rekommenderas 2.5 mm² kopparkabel för att hålla spänningsfallet under 3% (4.28V / 1.86%).

Hur stor effekt motsvarar 10A vid 230V?

Det motsvarar 2.3 kW med en rekommenderad säkring på 10A.