Kabelarea för 10 Ampere vid 90 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 10 A över 90 m vid 400V.

Copper Cable (≤3% Drop)4 mm²Drop: 8.34V (2.08%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 9.17V (2.29%)
Voltage at Load391.7 VLine Loss: 144.4 W
Max Power & Breaker6.93 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A22.24 V (5.56%)377.8 V36.68 V (9.17%)385.2 WDrop High
2.5 mm²24 A18 A13.34 V (3.34%)386.7 V22.01 V (5.5%)231.1 W~ ≤5%
4 mm²32 A25 A8.34 V (2.08%)391.7 V13.76 V (3.44%)144.4 W✓ OK (≤3%)
6 mm²41 A32 A5.56 V (1.39%)394.4 V9.17 V (2.29%)96.3 W✓ OK (≤3%)
10 mm²57 A44 A3.34 V (0.83%)396.7 V5.5 V (1.38%)57.8 W✓ OK (≤3%)
16 mm²76 A59 A2.08 V (0.52%)397.9 V3.44 V (0.86%)36.1 W✓ OK (≤3%)
25 mm²101 A78 A1.33 V (0.33%)398.7 V2.2 V (0.55%)23.1 W✓ OK (≤3%)
35 mm²125 A97 A0.95 V (0.24%)399.0 V1.57 V (0.39%)16.5 W✓ OK (≤3%)
50 mm²151 A118 A0.67 V (0.17%)399.3 V1.1 V (0.28%)11.6 W✓ OK (≤3%)
70 mm²192 A150 A0.48 V (0.12%)399.5 V0.79 V (0.2%)8.3 W✓ OK (≤3%)
95 mm²232 A181 A0.35 V (0.09%)399.6 V0.58 V (0.14%)6.1 W✓ OK (≤3%)
120 mm²269 A210 A0.28 V (0.07%)399.7 V0.46 V (0.11%)4.8 W✓ OK (≤3%)
150 mm²309 A241 A0.22 V (0.06%)399.8 V0.37 V (0.09%)3.9 W✓ OK (≤3%)
185 mm²353 A275 A0.18 V (0.05%)399.8 V0.3 V (0.07%)3.1 W✓ OK (≤3%)
240 mm²415 A324 A0.14 V (0.03%)399.9 V0.23 V (0.06%)2.4 W✓ OK (≤3%)
300 mm²477 A372 A0.11 V (0.03%)399.9 V0.18 V (0.05%)1.9 W✓ OK (≤3%)
400 mm²570 A445 A0.08 V (0.02%)399.9 V0.14 V (0.03%)1.4 W✓ OK (≤3%)

FAQ — Kabelarea för 10 Ampere vid 90 Meter (400V)

Vilken kabelarea krävs för 10A vid 90 meter (400V)?

För 10 Ampere över 90 meter vid 400V rekommenderas 4 mm² kopparkabel för att hålla spänningsfallet under 3% (8.34V / 2.08%).

Hur stor effekt motsvarar 10A vid 400V?

Det motsvarar 6.93 kW med en rekommenderad säkring på 10A.