Kabelarea för 125 Ampere vid 90 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 125 A över 90 m vid 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 11.91V (2.98%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 9.83V (2.46%)
Voltage at Load388.1 VLine Loss: 2579.5 W
Max Power & Breaker86.6 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A277.99 V (69.5%)122.0 V458.56 V (114.64%)60187.5 WDrop High
2.5 mm²24 A18 A166.8 V (41.7%)233.2 V275.14 V (68.78%)36112.5 WDrop High
4 mm²32 A25 A104.25 V (26.06%)295.8 V171.96 V (42.99%)22570.3 WDrop High
6 mm²41 A32 A69.5 V (17.37%)330.5 V114.64 V (28.66%)15046.9 WDrop High
10 mm²57 A44 A41.7 V (10.42%)358.3 V68.78 V (17.2%)9028.1 WDrop High
16 mm²76 A59 A26.06 V (6.52%)373.9 V42.99 V (10.75%)5642.6 WDrop High
25 mm²101 A78 A16.68 V (4.17%)383.3 V27.51 V (6.88%)3611.2 WDrop High
35 mm²125 A97 A11.91 V (2.98%)388.1 V19.65 V (4.91%)2579.5 W✓ OK (≤3%)
50 mm²151 A118 A8.34 V (2.08%)391.7 V13.76 V (3.44%)1805.6 W✓ OK (≤3%)
70 mm²192 A150 A5.96 V (1.49%)394.0 V9.83 V (2.46%)1289.7 W✓ OK (≤3%)
95 mm²232 A181 A4.39 V (1.1%)395.6 V7.24 V (1.81%)950.3 W✓ OK (≤3%)
120 mm²269 A210 A3.47 V (0.87%)396.5 V5.73 V (1.43%)752.3 W✓ OK (≤3%)
150 mm²309 A241 A2.78 V (0.69%)397.2 V4.59 V (1.15%)601.9 W✓ OK (≤3%)
185 mm²353 A275 A2.25 V (0.56%)397.7 V3.72 V (0.93%)488.0 W✓ OK (≤3%)
240 mm²415 A324 A1.74 V (0.43%)398.3 V2.87 V (0.72%)376.2 W✓ OK (≤3%)
300 mm²477 A372 A1.39 V (0.35%)398.6 V2.29 V (0.57%)300.9 W✓ OK (≤3%)
400 mm²570 A445 A1.04 V (0.26%)399.0 V1.72 V (0.43%)225.7 W✓ OK (≤3%)

FAQ — Kabelarea för 125 Ampere vid 90 Meter (400V)

Vilken kabelarea krävs för 125A vid 90 meter (400V)?

För 125 Ampere över 90 meter vid 400V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (11.91V / 2.98%).

Hur stor effekt motsvarar 125A vid 400V?

Det motsvarar 86.6 kW med en rekommenderad säkring på 125A.