Kabelarea för 32 Ampere vid 90 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 32 A över 90 m vid 400V.
Copper Cable (≤3% Drop)10 mm²Drop: 10.67V (2.67%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 11.01V (2.75%)
Voltage at Load389.3 VLine Loss: 591.7 W
Max Power & Breaker22.17 kW32A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 90m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 71.17 V (17.79%) | 328.8 V | 117.39 V (29.35%) | 3944.4 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 42.7 V (10.67%) | 357.3 V | 70.43 V (17.61%) | 2366.7 W | Drop High |
| 4 mm² | 32 A | 25 A | 26.69 V (6.67%) | 373.3 V | 44.02 V (11.01%) | 1479.2 W | Drop High |
| 6 mm² | 41 A | 32 A | 17.79 V (4.45%) | 382.2 V | 29.35 V (7.34%) | 986.1 W | ~ ≤5% |
| 10 mm² | 57 A | 44 A | 10.67 V (2.67%) | 389.3 V | 17.61 V (4.4%) | 591.7 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 6.67 V (1.67%) | 393.3 V | 11.01 V (2.75%) | 369.8 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 4.27 V (1.07%) | 395.7 V | 7.04 V (1.76%) | 236.7 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 3.05 V (0.76%) | 397.0 V | 5.03 V (1.26%) | 169.0 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 2.13 V (0.53%) | 397.9 V | 3.52 V (0.88%) | 118.3 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 1.52 V (0.38%) | 398.5 V | 2.52 V (0.63%) | 84.5 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 1.12 V (0.28%) | 398.9 V | 1.85 V (0.46%) | 62.3 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.89 V (0.22%) | 399.1 V | 1.47 V (0.37%) | 49.3 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.71 V (0.18%) | 399.3 V | 1.17 V (0.29%) | 39.4 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.58 V (0.14%) | 399.4 V | 0.95 V (0.24%) | 32.0 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.44 V (0.11%) | 399.6 V | 0.73 V (0.18%) | 24.7 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.36 V (0.09%) | 399.6 V | 0.59 V (0.15%) | 19.7 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.27 V (0.07%) | 399.7 V | 0.44 V (0.11%) | 14.8 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 32 Ampere vid 90 Meter (400V)
Vilken kabelarea krävs för 32A vid 90 meter (400V)?
För 32 Ampere över 90 meter vid 400V rekommenderas 10 mm² kopparkabel för att hålla spänningsfallet under 3% (10.67V / 2.67%).
Hur stor effekt motsvarar 32A vid 400V?
Det motsvarar 22.17 kW med en rekommenderad säkring på 32A.
Related Lengths & Currents (400V)
32A · 5m (400V)32A · 10m (400V)32A · 15m (400V)32A · 20m (400V)32A · 25m (400V)32A · 30m (400V)32A · 35m (400V)32A · 40m (400V)32A · 45m (400V)32A · 50m (400V)32A · 60m (400V)32A · 70m (400V)10A · 90m (400V)16A · 90m (400V)20A · 90m (400V)25A · 90m (400V)40A · 90m (400V)50A · 90m (400V)63A · 90m (400V)80A · 90m (400V)100A · 90m (400V)125A · 90m (400V)160A · 90m (400V)200A · 90m (400V)