Kabelarea för 15 Ampere vid 100 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 15 A över 100 m vid 230V.

Copper Cable (≤3% Drop)10 mm²Drop: 6.42V (2.79%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 6.62V (2.88%)
Voltage at Load223.6 VLine Loss: 96.3 W
Max Power & Breaker3.45 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A42.8 V (18.61%)187.2 V70.6 V (30.7%)642.0 WDrop High
2.5 mm²24 A18 A25.68 V (11.17%)204.3 V42.36 V (18.42%)385.2 WDrop High
4 mm²32 A25 A16.05 V (6.98%)213.9 V26.47 V (11.51%)240.7 WDrop High
6 mm²41 A32 A10.7 V (4.65%)219.3 V17.65 V (7.67%)160.5 W~ ≤5%
10 mm²57 A44 A6.42 V (2.79%)223.6 V10.59 V (4.6%)96.3 W✓ OK (≤3%)
16 mm²76 A59 A4.01 V (1.74%)226.0 V6.62 V (2.88%)60.2 W✓ OK (≤3%)
25 mm²101 A78 A2.57 V (1.12%)227.4 V4.24 V (1.84%)38.5 W✓ OK (≤3%)
35 mm²125 A97 A1.83 V (0.8%)228.2 V3.03 V (1.32%)27.5 W✓ OK (≤3%)
50 mm²151 A118 A1.28 V (0.56%)228.7 V2.12 V (0.92%)19.3 W✓ OK (≤3%)
70 mm²192 A150 A0.92 V (0.4%)229.1 V1.51 V (0.66%)13.8 W✓ OK (≤3%)
95 mm²232 A181 A0.68 V (0.29%)229.3 V1.11 V (0.48%)10.1 W✓ OK (≤3%)
120 mm²269 A210 A0.53 V (0.23%)229.5 V0.88 V (0.38%)8.0 W✓ OK (≤3%)
150 mm²309 A241 A0.43 V (0.19%)229.6 V0.71 V (0.31%)6.4 W✓ OK (≤3%)
185 mm²353 A275 A0.35 V (0.15%)229.7 V0.57 V (0.25%)5.2 W✓ OK (≤3%)
240 mm²415 A324 A0.27 V (0.12%)229.7 V0.44 V (0.19%)4.0 W✓ OK (≤3%)
300 mm²477 A372 A0.21 V (0.09%)229.8 V0.35 V (0.15%)3.2 W✓ OK (≤3%)
400 mm²570 A445 A0.16 V (0.07%)229.8 V0.26 V (0.12%)2.4 W✓ OK (≤3%)

FAQ — Kabelarea för 15 Ampere vid 100 Meter (230V)

Vilken kabelarea krävs för 15A vid 100 meter (230V)?

För 15 Ampere över 100 meter vid 230V rekommenderas 10 mm² kopparkabel för att hålla spänningsfallet under 3% (6.42V / 2.79%).

Hur stor effekt motsvarar 15A vid 230V?

Det motsvarar 3.45 kW med en rekommenderad säkring på 15A.